Third Notice ELE | 4/26/2006 | 4/26/2006 | 5/2/2006 | | DONE |
|
|
|
This permit finaled on the web by Kathy Briggs
|
Second Notice ELE | 3/31/2006 | 3/31/2006 | 4/26/2006 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice | 3/17/2006 | 3/17/2006 | 3/31/2006 | | DONE |
Bob Reichert
|
|
|
|
Final | 3/17/2006 | 3/20/2006 | 3/20/2006 | A | CANC |
Bob Reichert
|
|
|
chad ; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa done Fri pm,
|
Final | 3/17/2006 | 3/17/2006 | 3/17/2006 | P | PASS |
Bob Reichert
|
|
|
contr made corrections, called to see if we could re-inspect. ok to final, signed occ card
|
Final | 3/17/2006 | 3/17/2006 | 3/17/2006 | P | FAIL |
Bob Reichert
|
|
|
met with 315 and contr, corr not done, they will call for Mon am
|
Final | 3/16/2006 | 3/17/2006 | 3/17/2006 | A | CANC |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Kathy Briggs see added conf.
|
Conference | 3/17/2006 | 3/17/2006 | 3/17/2006 | P | DONE |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Kathy Briggs met with Bob R and contractor we disccussed the violations Bob posted and contractor did not correct
|
Final | 3/10/2006 | 3/10/2006 | 3/10/2006 | P | PART |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Kathy Briggs met contr, left corr notice, did not sign card,330.30(B) mc cable shall be supported within 12" of box,314.27(C) floor box covers shall be listed as part of assembly,348.30(A) flex metal conduit shall be secured within 12" of box,210.62 show room receptacles shall be installed, 358.30 emt shall be secured within 3' of box, 400.8 flexible cords shall not be used as a substitute for fixed wiring, 408.4 circuit directories shall be completed, 110.3(A) only listed equipment shall be installed, 300.4 conductors shall be protected where subject to physical damage
|
Electrical Rough-In | 2/28/2006 | 3/1/2006 | 3/1/2006 | A | PASS |
Bob Reichert
|
|
|
Ceiling inspection.; Phone #: ###-#### Internet Inspection Request from: Kathy Briggs ok to cover ceilings
|
Rough-In Permanent Service | 2/1/2006 | 2/2/2006 | 2/2/2006 | A | CANC |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Kathy Briggs see p/s
|
Permanent Service | 2/2/2006 | 2/2/2006 | 2/2/2006 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Kathy Briggs p/s u/g n ok
|
Electrical Rough-In | 1/16/2006 | 1/16/2006 | 1/17/2006 | P | PASS |
Mike Kinnear
|
|
|
Interior wall inspection.; Phone #: ###-#### Internet Inspection Request from: Kathy Briggs ok cover walls only
|
Electrical Rough-In | 11/17/2005 | 11/17/2005 | 11/17/2005 | P | PART |
Bob Reichert
|
|
|
Underground inspection.; Phone #: ###-#### Internet Inspection Request from: Kathy Briggs ok to cover u/g from xfmr to riser in future bldg and to ne corner of lot
|
Electrical Rough-In | 11/16/2005 | 11/17/2005 | 11/17/2005 | A | FAIL |
Bob Reichert
|
|
|
Underground inspection.; Phone #: ###-#### Internet Inspection Request from: Kathy Briggs had contr dig up u/g, not deep enough, elect on job, they will fix and recall
|
Electrical Rough-In | 10/25/2005 | 10/25/2005 | 10/25/2005 | P | PASS |
Bob Reichert
|
|
|
Ufer inspection. Ufer is straight away from pole in foundation.; Phone #: ###-#### Internet Inspection Request from: Kathy Briggs ok to cover gec, left sticker on gec.
|
Application received | | | 10/25/2005 | | DONE |
|
|
|
This permit was created on the web by Kathy Briggs
|