Final | 1/11/2006 | 1/11/2006 | 1/11/2006 | P | PASS |
Bob Reichert
|
|
|
cody ###-#### for access called contr, left message, left survey,406.4 front recpt shall be rigidly held in place, ok to final
|
Final | 1/10/2006 | 1/11/2006 | 1/11/2006 | A | CANC |
Bob Reichert
|
|
|
call for garage code///cody; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa called contr for access, code won't work, said they will have to recall.
|
Electrical Rough-In | 10/28/2005 | 10/28/2005 | 10/28/2005 | P | PASS |
Bob Reichert
|
|
|
###-#### corr made, ric ok, p/s u/g n ok
|
Electrical Rough-In | 10/26/2005 | 10/26/2005 | 10/26/2005 | P | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Nicole Richardson called contr left corr notice,BCC shall provide address and job id sticker,312.5 gec shall have abrasion protection, 250.68 gec shall be accessible,110.12(A) unused openings shall be closed, 300.4(A)(1) and (D) bored holes and nm cable shall be 1 1/4" from edge of framing member,110.12(C) there shall be no damaged cable
|
Application received | | | 10/26/2005 | | DONE |
|
|
|
This permit was created on the web by Nicole Richardson
|