Second Notice ELE | 4/26/2006 | 4/26/2006 | 4/27/2006 | | DONE |
|
|
|
This permit finaled on the web by Randy Vail
|
Second Notice ELE | 4/26/2006 | 4/26/2006 | 4/27/2006 | | DONE |
|
|
|
This permit finaled on the web by Randy Vail
|
First Notice | 4/13/2006 | 4/13/2006 | 4/26/2006 | | DONE |
Jack Frank
|
|
|
|
First Notice | 4/12/2006 | 4/12/2006 | 4/26/2006 | | DONE |
Mike Kinnear
|
|
|
|
Final | 4/12/2006 | 4/13/2006 | 4/13/2006 | P | PASS |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Randy Vail was done 04-12-06 by 412
|
Final | 4/12/2006 | 4/12/2006 | 4/12/2006 | P | PASS |
Mike Kinnear
|
|
|
Phone #: ###-#### Internet Inspection Request from: Randy Vail corrections made ok final
|
Final | 4/10/2006 | 4/10/2006 | 4/10/2006 | P | FAIL |
Jack Frank
|
|
|
PLEASE CALL DAVE BRADSHAW & HE WILL MEET THE INSPECTOR @ THE JOBSITE; Phone #: ###-#### Internet Inspection Request from: Randy Vail corr. called 250.8 no SMS allowed for grds or bonds, 310.15 (B)(2) table derate at 50%, 250.122(B) shall increase equip grds also for size, 250.12shall remove paint for clean surface at equip grd bus j box,, 250.126 for equip grd bus at jbox
|
Final | 4/5/2006 | 4/5/2006 | 4/5/2006 | P | NR |
Jack Frank
|
|
|
PLEASE CALL DAVE BRADSHAW & HE WILL MEET @ JOBSITE; Phone #: ###-#### Internet Inspection Request from: Randy Vail met nwith dave needs clearence for panel with gas meters under them they will correct and reschedule
|
Permanent Service | 3/23/2006 | 3/27/2006 | 3/27/2006 | P | PASS |
Jack Frank
|
|
|
PLEASE CALL DAVE BRADSHAW TO MEET INSPECTOR ON SITE; Phone #: ###-#### Internet Inspection Request from: Randy Vail r/i for new subpanel ok
|
Permanent Service | 3/23/2006 | 3/24/2006 | 3/24/2006 | P | PASS |
Bob Reichert
|
|
|
PLEASE CALL DAVE BRADSHAW TO MEET INSPECTOR ON SITE; Phone #: ###-#### Internet Inspection Request from: Randy Vail looked at fittings, ok, p/s, unit 7009 ok for meter
|
Permanent Service | 3/20/2006 | 3/21/2006 | 3/21/2006 | P | PASS |
William E Thomas
|
|
|
PLEASE CALL DAVE BRADSHAW AND HE WILL MEET THE INSPECTOR; Phone #: ###-#### Internet Inspection Request from: Randy Vail p/s ok - unit 7005 on the meter packs
|
Permanent Service | 3/17/2006 | 3/20/2006 | 3/20/2006 | P | PASS |
Bob Reichert
|
|
|
PLEASE CALL DAVE BRADSHAW & HE WILL MEET INSPECTOR AT JOBSITE; Phone #: ###-#### Internet Inspection Request from: Randy Vail ok to install 2 meters in approved service line-up, services are located outside and feed to sub-panels in tenant spaces
|
Permanent Service | 2/10/2006 | 2/13/2006 | 2/13/2006 | A | PASS |
Jack Frank
|
|
|
APPROVE SERVICE FOR IDAHO POWER HOOKUP; Phone #: ###-#### Internet Inspection Request from: Randy Vail p/s o/h rec. ok
|
Final | 2/1/2006 | 2/1/2006 | 2/1/2006 | P | NR |
Jack Frank
|
|
|
REINSPECTION OF SERVICE; Phone #: ###-#### Internet Inspection Request from: Randy Vail no final conference ok only when ready needs to call for p/s not final
|
Permanent Service | 1/31/2006 | 1/31/2006 | 1/31/2006 | P | NR |
Mike Kinnear
|
|
|
Phone #: ###-#### Internet Inspection Request from: Randy Vail t/w don rye we need to meet with electrician who did the work. he to call for appointment. note grounding, bonding, & sub panels need to be addressed. neutral bonded to the meter base?
|
ELE-Aging Inspection | 1/26/2006 | 1/26/2006 | 1/26/2006 | | CANC |
Jack Frank
|
|
|
wsuc
|
Application received | | | 10/27/2005 | | DONE |
|
|
|
This permit was created on the web by Randy Vail
|