Final | 5/31/2006 | 5/31/2006 | 5/31/2006 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung corrections made, ok to final
|
Final | 5/30/2006 | 5/31/2006 | 5/31/2006 | A | FAIL |
Bob Reichert
|
|
|
call first ; Phone #: ###-#### Internet Inspection Request from: Rita DeYoung called contr, left corr notice, nec 352.30(A) rnc shall be supported within 3' of panel,250.64(B) gec shall be secured to surface, 408.4 circuit directory shall be provided,110.3(B) disposal shall be wired, reverse polarity on recpt on island shall be corrected, 422.31(B) furnace disconnect shall be supplied
|
Permanent Service | 5/2/2006 | 5/3/2006 | 5/3/2006 | A | PASS |
Bob Reichert
|
|
|
kelly; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles p/s u/g n ok
|
Electrical Rough-In | 11/23/2005 | 11/23/2005 | 11/23/2005 | A | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 11/23/2005 at 7:29:25 AM. Contact: ###-####. ric ok, corrections made
|
Electrical Rough-In | 11/7/2005 | 11/7/2005 | 11/7/2005 | P | FAIL |
Bob Reichert
|
|
|
kelly; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles no panel set, talked to elect, left corr notice, 210.52(A)(2) recpt shall be added in entry area wall, 210.52(F) recpt shall be added at rear of dwelling, 314.20 boxes shall be flush with combustible material, 334.30 nm cable shall be supported within 12" of boxs, 300.4(A)(1) edge of bored hole shall be 1 1/4" from edgfe of framing member, 800.133(A)(1) comm cable shall not be run with power cables
|
Application received | | | 11/4/2005 | | DONE |
|
|
|
This permit was created on the web by Deb McCoy
|