Final | 2/16/2006 | 2/17/2006 | 2/17/2006 | A | PASS |
Bob Reichert
|
|
|
garage code is 1234 Internet Inspection Request from: Cevyn Recla corrections made, ok to final
|
Final | 2/15/2006 | 2/16/2006 | 2/16/2006 | A | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Cevyn Recla 408.4 panel sched shall be complete and concise, 350.26 there shall not be more than 360 degree bends in flex, 210.52(D) receptacle shall be within 3' of basin, 422.31(B) there shall be a lockable breaker for dishwasher, 404.9 faceplates shall seat against finished surface, 406.4 receptacles shall be securely fastened in place, BCC there shall be no household goods in front of areas to be inspected
|
Rough-In Permanent Service | 11/15/2005 | 11/15/2005 | 11/15/2005 | P | PASS |
William E Thomas
|
|
|
Phone #: ###-#### Internet Inspection Request from: Cevyn Recla ri ok p/s u/g n ok
|
Rough-In Permanent Service | 11/14/2005 | 11/15/2005 | 11/15/2005 | A | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Cevyn Recla called cont, left corr notice,312.5 conductors shall be protected from abrasion, 800.133(A)(1) class 2 conductors shall not be run with class 1 ,300.4(A)&(D) 1 1/4" shall be maintained from edge of structural member,314.20 box shall be flush with combustible wall, BCC job id sticker shall be posted
|
Application received | | | 11/7/2005 | | DONE |
|
|
|
This permit was created on the web by Cevyn Recla
|