Final | 2/8/2006 | 2/9/2006 | 2/9/2006 | A | PASS |
Bob Reichert
|
|
|
Brian; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong corrections made, ok to final
|
Final | 2/8/2006 | 2/8/2006 | 2/8/2006 | P | FAIL |
Bob Reichert
|
|
|
dan; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa called contr, left corr notice, 680.73 electrical equipment for tub shall be accessible without damaging building, 406.5 recpt faceplate shall seat against mounting surface (upper bath), 406.4 recpts shall be securely fastened in place(front room, north side), 110.3(B) listed equipment shall be installed in accordance with instructions(mbr closet light lens)
|
Rough-In Permanent Service | 11/14/2005 | 11/15/2005 | 11/15/2005 | A | PASS |
Bob Reichert
|
|
|
brian ; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa corr made, ric ok, p/s u/g n ok
|
Rough-In Permanent Service | 11/14/2005 | 11/14/2005 | 11/14/2005 | P | FAIL |
Bob Reichert
|
|
|
brian ###-#### called contr, left corr notice, 300.4(A)&(D) 1 1/4" shall be maintained for bored holes and nm cable shall be from edge of framing member, 800.133(A)(1) comm cable shall not be run with class 1 wiring,110.12(A) there shall be no open wiring holes in boxes, 314.20 boxes shall be flush with combustibloe material (out back recpt), BCC job id sticker shall be posted
|
Issue permit | | | 11/14/2005 | | DONE |
|
|
|
|
Application received | | | 11/14/2005 | | |
|
|
|
|