Second Notice ELE | 3/15/2006 | 3/15/2006 | 3/24/2006 | | DONE |
|
|
|
This permit finaled on the web by Rick Beckman
|
First Notice | 2/27/2006 | 2/27/2006 | 3/15/2006 | | DONE |
Jack Frank
|
|
|
|
Final | 2/27/2006 | 2/28/2006 | 2/27/2006 | A | PASS |
Jack Frank
|
|
|
rick; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa ok card signed
|
Final | 2/21/2006 | 2/22/2006 | 2/22/2006 | A | FAIL |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 2/21/2006 at 4:29:14 PM. Contact: ###-####. cor. called 110.26 needs clearence sub panel in cabinet, 250.148 terminate all equip grds, in disconnects on roof also needs #10 equip grd for 30 amp on roof 250.122, 300.11(B) shall not secure phone to flex cash area314.25 covers for all boxes, 314.23(E) support boxes on roof with only 1 conduit, note all wiring shall be complete high and low voltages also control wiring done on permit #ele06-00570
|
Electrical Rough-In | 2/15/2006 | 2/16/2006 | 2/16/2006 | A | FAIL |
William E Thomas
|
|
|
Scheduled by a contractor via Hello! on 2/15/2006 at 3:57:14 PM. Contact: ###-####. 1. electrical contractor cieling ok, low voltage work still needs to be complete for cover inspection.
|
Permanent Service | 1/30/2006 | 1/30/2006 | 1/30/2006 | P | PASS |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 1/30/2006 at 9:12:05 AM. Contact: ###-####. p/s u/g n ok
|
Permanent Service | 1/29/2006 | 1/30/2006 | 1/30/2006 | A | NR |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 1/29/2006 at 3:30:18 PM. Contact: ###-####. called
|
Permanent Service | 1/27/2006 | 1/27/2006 | 1/27/2006 | P | NR |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 1/27/2006 at 9:39:30 AM. Contact: ###-####. called
|
Electrical Rough-In | 1/5/2006 | 1/5/2006 | 1/5/2006 | P | PART |
Jack Frank
|
|
|
rick; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa walls hard ceiling ok
|
Electrical Rough-In | 11/15/2005 | 11/16/2005 | 11/16/2005 | A | PASS |
Pat Lass
|
|
|
Scheduled by a contractor via Hello! on 11/15/2005 at 8:23:33 PM. Contact: ###-####. U/G ok
|
Electrical Rough-In | 11/14/2005 | 11/14/2005 | 11/14/2005 | P | PART |
Jack Frank
|
|
|
rick ###-#### -call 1st before insp u/g from new store to carwash
|
Issue & PRINT permit | | | 11/14/2005 | | DONE |
|
|
|
|
Application received | | | 11/14/2005 | | |
|
|
|
|
Owner Supplied Equipment | 11/14/2005 | | | | |
|
|
|
|