Second Notice ELE | 2/27/2006 | 2/27/2006 | 2/27/2006 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice | 1/30/2006 | 1/30/2006 | 2/27/2006 | | DONE |
Jack Frank
|
|
|
|
ELE-Aging Inspection | 1/30/2006 | 1/30/2006 | 1/30/2006 | | PASS |
Jack Frank
|
|
|
|
Final | 1/30/2006 | 1/30/2006 | 1/30/2006 | P | PASS |
Jack Frank
|
|
|
ok
|
Temporary Service | 11/16/2005 | 11/17/2005 | 11/17/2005 | A | PART |
Jack Frank
|
|
|
Re-inspection after corrections made. Contact is Perry.; Phone #: ###-#### Internet Inspection Request from: David Bonner needs to wire job shack t/s o/h new ok for hook up
|
Temporary Service | 11/14/2005 | 11/15/2005 | 11/15/2005 | A | FAIL |
Jack Frank
|
|
|
Contact is Jeff.; Phone #: ###-#### Internet Inspection Request from: David Bonner cor. called 110.12 seal KOs, 110.3 & 300.10 needs bond bushings where RE washers are used, connector in myers hub cross threaded, 250.90,92 needs listed myers hub for service bonding requirements, 590.6(B) all recepts 240 volt need gfci protection
|
Application received | | | 11/14/2005 | | DONE |
|
|
|
This permit was created on the web by David Bonner
|