Permit Information
Permit NumberELE05-04236
StatusFinaled
Name SNAKE RIVER ELECTRIC INC
Site Address 11801 W EXECUTIVE DR
Project Name 
Customer Number 
ePlanReview 
Description
11/22/2005 - install electrical rec and lights in new office area - $4197.00 per initial cert of value - cmc ///Final value is $4,697//2/13/06 LEG
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Third Notice ELE2/9/20062/9/20062/13/2006 DONE
Second Notice has not been responded to.
Second Notice ELE1/25/20061/25/20062/9/2006 DONE
First Notice has not been responded to.
First Notice1/10/20061/10/20061/25/2006 DONE
DetailsBob Reichert
Final1/10/20061/10/20061/10/2006PPASS
DetailsBob Reichert
Scheduled by a contractor via Hello! on 1/10/2006 at 7:40:15 AM. Contact: ###-####. signed struct card, ok to final
Final12/13/200512/14/200512/14/2005PCANC
DetailsBob Reichert
Scheduled by a contractor via Hello! on 12/13/2005 at 10:25:43 PM. Contact: ###-####. see ri
Electrical Rough-In12/14/200512/14/200512/14/2005PPASS
DetailsBob Reichert
Scheduled by a contractor via Hello! on 12/13/2005 at 10:25:43 PM. Contact: ###-####. ok to cover ceiling, will do final ltr
Final12/7/200512/7/200512/7/2005PFAIL
DetailsBob Reichert
ceiling/final////stu; Phone #: ###-#### Internet Inspection Request from: Barbara Moore called contr, left corr notice, 300.11(A) ceiling wires shall be identified, 800.154(A) abandoned comm wires shall be removed, 210.62 show room recpts shall be installed, 314.25 boxes shall have covers installed, 404.9(A) sws shall have covers installed,406.5 recpts shall shall have faceplates installed,408.4 circuit directory shall be complete and detailed, 800.24 communications cable shall be supported, BCC no violations shall be retained
Electrical Rough-In11/23/200511/23/200511/23/2005PPASS
DetailsMike Kinnear
Scheduled by a contractor via Hello! on 11/23/2005 at 7:53:09 AM. Contact: ###-####. ok cover walls only
Electrical Rough-In11/22/200511/22/200511/22/2005PPART
DetailsJack Frank
###-#### - stu 1 room ok called needs to replace cutin box front wall with bigger one for fill
Issue permit  11/22/2005 DONE
Application received  11/22/2005