Information based on query as of Thursday, July 18, 2024.
Permit Information
Permit NumberELE05-04249
StatusFinaled
Name C H ELECTRIC
Site Address 9568 W CANTERBURY DR
Project Name 
Customer Number 
ePlanReview 
Description
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Temporary Service11/29/200511/30/200511/30/2005APASS
DetailsBob Reichert
chris; Phone #: ###-#### Internet Inspection Request from: Barbara Moore corr made, t/s u/g n ok
Temporary Service11/23/200511/23/200511/23/2005PFAIL
DetailsBob Reichert
###-####-chris called contr, left corr notice, 312.5 conductors entering enclosures shall have abrasion protection, 250.52(A)(5)(b) ground rod shall be 5/8" diameter, fee due
Stop Work/Reinspection Fee11/23/200511/23/200511/23/2005PFAIL
DetailsBob Reichert
see inspection description
Application received  11/23/2005  
Issue permit  11/23/2005 DONE