Final | 1/9/2006 | 1/9/2006 | 1/9/2006 | P | PASS |
Jack Frank
|
|
|
rick; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok notice posted , permit needed for spa and shed wiring
|
Electrical Rough-In | 12/6/2005 | 12/6/2005 | 12/6/2005 | P | PASS |
Jack Frank
|
|
|
rick - re-insp ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie garage addition and spa disconnect ok
|
Electrical Rough-In | 12/2/2005 | 12/2/2005 | 12/2/2005 | P | FAIL |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 12/2/2005 at 11:13:35 AM. Contact: ###-####. r/i for u/g ok only, called needs to update permit for p/s and 1 rm, needs shed to meet part II of art 225, 250.32, 210.70
|
Electrical Rough-In | 11/28/2005 | 11/29/2005 | 11/29/2005 | A | FAIL |
Bob Reichert
|
|
|
rick ###-#### called contr, left message, left corr notice,352.30(A) rnc shall be securely supported within 3' of termination, 250.32(A) grounding electrodes shall be installed,BCC underground shall be inspected before cover
|
Issue permit | | | 11/28/2005 | | DONE |
|
|
|
|
Application received | | | 11/28/2005 | | |
|
|
|
|