Telephone call | | | 12/12/2012 | | DONE |
Christina Prado
|
|
|
Per Bob A & Doug P - ok to pay 1hr admin fee to reopen permit for final inspection. New ELE permit is required to be pulled with new contractor and finaled prior to BLD final. ELE permit fee is to be $46.31
|
DOC - Permit Expired | 12/22/2011 | 12/22/2011 | 12/22/2011 | A | PASS |
Jack Frank
|
|
|
note new contr will secure permit correct all violations and finish job then request final inspection when all that is completed
|
Final | 10/6/2011 | 10/6/2011 | 10/6/2011 | P | CANC |
Jack Frank
|
|
|
junior - please call 1/2 hr prior Phone #: ###-#### called new contr he is checking out job , and will escure permit for the work he does
|
Change Status to I | | | 10/6/2011 | | DONE |
|
|
|
re-open for final inspection
|
ELE-Aging Inspection | 9/23/2011 | 9/23/2011 | 9/23/2011 | | DONE |
Jack Frank
|
|
|
see added doc expire, and notes
|
DOC - Permit Expired | 9/23/2011 | 9/23/2011 | 9/23/2011 | A | PASS |
Jack Frank
|
|
|
talked with owner told them they need to hire ele. contr., he will secure permit and take over job, and correct all violations 370 had noted
|
Final | 6/24/2011 | 6/29/2011 | 6/29/2011 | P | FAIL |
Jack Frank
|
|
|
Jayne Blazek (tenant), work was already done a long time ago, just never scheduled inspection. Phone #: ###-#### already talked with Jayne, there are supposed to hire electrical contractor to take over job and finish what 1st contractor did not finish see failed final inspection request by Bob
|
Final | 5/23/2011 | 5/26/2011 | 5/26/2011 | P | NR |
Jack Frank
|
|
|
Jane Phone #: ###-#### talked with owner they will hire new contractor to take over work
|
CHANGE STATUS TO I | | | 5/23/2011 | | DONE |
Barbara Stitt
|
|
|
Re-open for final per Bob Archibald 5-23-11
|
Case Summary (ELE) | | | 5/23/2011 | | DONE |
|
|
|
|
Miscellaneous action | | | 5/20/2011 | | PEND |
Bob Archibald
|
|
|
Electrical contractor may reactivate for final inspection. 1 hour admin. fee required. Bob A.
|
ELE-Aging Inspection | 4/24/2007 | 4/24/2007 | 4/26/2007 | | PART |
Jack Frank
|
|
|
talked with contractor told him permit will be expired his never called back or did anything
|
DOC - Permit Expired | 4/26/2007 | 4/26/2007 | 4/26/2007 | A | PASS |
Jack Frank
|
|
|
|
ELE-Aging Inspection | 2/22/2007 | 2/22/2007 | 2/26/2007 | | PART |
Jack Frank
|
|
|
called talked with contractor hr will check out status of job
|
ELE-Aging Inspection | 12/14/2006 | 12/14/2006 | 12/15/2006 | | PART |
Jack Frank
|
|
|
|
ELE-Aging Inspection | 10/5/2006 | 10/5/2006 | 10/5/2006 | | NR |
Bob Reichert
|
|
|
not ready yet
|
ELE-Aging Inspection | 8/4/2006 | 8/4/2006 | 8/7/2006 | | NR |
Bob Reichert
|
|
|
talked to elect and struct, waiting for contr to call
|
ELE-Aging Inspection | 5/31/2006 | 5/31/2006 | 6/2/2006 | | DONE |
Bob Reichert
|
|
|
called contr, still not ready for final, open corr notice
|
Final | 3/28/2006 | 3/28/2006 | 3/28/2006 | P | FAIL |
Bob Reichert
|
|
|
Robert -- location back of office; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong called contr, set up meeting when he calls back in, 314.23(C) enclosure mounted in finished surface shall be rigidly secured, BCC ceiling cover not approved
|
ELE-Aging Inspection | 3/22/2006 | 3/22/2006 | 3/22/2006 | | DONE |
Bob Reichert
|
|
|
called contr to set up inspection, left message
|
Electrical Rough-In | 12/7/2005 | 12/7/2005 | 12/7/2005 | P | PASS |
Bob Reichert
|
|
|
robert; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corrections made, ric walls only ok
|
Electrical Rough-In | 12/6/2005 | 12/6/2005 | 12/6/2005 | P | FAIL |
Bob Reichert
|
|
|
robert; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr not complete
|
Electrical Rough-In | 12/1/2005 | 12/1/2005 | 12/1/2005 | P | FAIL |
Bob Reichert
|
|
|
robert --call 1st before insp for access; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie called contr, left corr notice, 358.30 emt shall be securely fastened within 3' of panel,330.17 mc cable shall be protected in accordance with 300.4(A)&(D) where installed through or parallel to framing members,300.4 mc cable subject to physical damage shall be protected, i.e. cable shall not be run inside valley of 2x4 studs, 110.26(F)(1)(b) there shall be no foreign piping above dedicated space unless protection is provided.
|
Application received | | | 11/29/2005 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 11/29/2005 | | DONE |
|
|
|
|