Third Notice ELE | 5/14/2007 | 5/14/2007 | 5/15/2007 | | DONE |
|
|
|
This permit finaled on the web by Jeff Durham
|
Second Notice ELE | 4/24/2007 | 4/24/2007 | 5/14/2007 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice | 4/6/2007 | 4/6/2007 | 4/24/2007 | | DONE |
Bob Reichert
|
|
|
|
Final | 4/5/2007 | 4/6/2007 | 4/6/2007 | A | PASS |
Bob Reichert
|
|
|
jason; Phone #: ###-#### Internet Inspection Request from: Stacie Backus corrections made, ok to final, signed occ card
|
Final | 3/22/2007 | 3/23/2007 | 3/23/2007 | A | PART |
Bob Reichert
|
|
|
jason; Phone #: ###-#### Internet Inspection Request from: Victoria Beall ok to final anop, signed t/o card, need to finish roof, fix corr notice, verify panel schedules
|
Final | 3/22/2007 | 3/22/2007 | 3/22/2007 | P | PART |
Bob Reichert
|
|
|
jason ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith 1st floor anop ok to final except pool equip room, left corr notice, nec 110.26(F)(1)(b) there shall be no foreign piping systems over dedicated panel space, NOTE: correction shall be made within 2 weeks or firther action will be taken such as removal of power
|
Final | 3/21/2007 | 3/21/2007 | 3/21/2007 | P | PART |
Mike Kinnear
|
|
|
jason; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok final anop 1st floor note ok light potting pool & tub
|
Final | 3/16/2007 | 3/19/2007 | 3/19/2007 | A | CANC |
Bob Reichert
|
|
|
jason; Phone #: ###-#### Internet Inspection Request from: Victoria Beall
|
Electrical Rough-In | 3/15/2007 | 3/15/2007 | 3/15/2007 | P | PART |
Jack Frank
|
|
|
Jason; Phone #: ###-#### Internet Inspection Request from: Stacie 1st floor ceilings ok
|
Electrical Rough-In | 3/13/2007 | 3/13/2007 | 3/13/2007 | P | FAIL |
Bob Reichert
|
|
|
jason; Phone #: ###-#### Internet Inspection Request from: Victoria Beall met elect, no tie wires for ceiling fixtures and low voltage wire on grid, did not want corr notice written, said would fix and recall
|
Final | 3/9/2007 | 3/12/2007 | 3/12/2007 | A | PART |
Bob Reichert
|
|
|
Jason; Phone #: ###-#### Internet Inspection Request from: Stacie Backus kitchen area ok to final anop
|
Electrical Rough-In | 3/8/2007 | 3/8/2007 | 3/8/2007 | P | PART |
Bob Reichert
|
|
|
jason; Phone #: ###-#### Internet Inspection Request from: Stacie Backus ok to cover ceilings, laundry and kitchen anop
|
Final | 2/22/2007 | 2/23/2007 | 2/23/2007 | A | PART |
Mike Kinnear
|
|
|
jason; Phone #: ###-#### Internet Inspection Request from: Victoria Beall ok cover & final hallways 2nd, 3rd & 4th floors
|
Electrical Rough-In | 2/15/2007 | 2/16/2007 | 2/16/2007 | A | PART |
Bob Reichert
|
|
|
JASON; Phone #: ###-#### Internet Inspection Request from: Victoria Beall ok to cover clgs anop 1st floor, some hard lid, some tile
|
Final | 2/13/2007 | 2/14/2007 | 2/14/2007 | A | PART |
Mike Kinnear
|
|
|
jason; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok final rms only anop
|
Final | 2/13/2007 | 2/13/2007 | 2/13/2007 | P | PART |
Bob Reichert
|
|
|
jason ; Phone #: ###-#### Internet Inspection Request from: Patricia 2nd floor, south part anop ok to final
|
Final | 2/6/2007 | 2/7/2007 | 2/7/2007 | A | CANC |
Mike Kinnear
|
|
|
jason; Phone #: ###-#### Internet Inspection Request from: Victoria Beall they called job not ready
|
Final | 2/2/2007 | 2/5/2007 | 2/5/2007 | A | PART |
Bob Reichert
|
|
|
JASON; Phone #: ###-#### Internet Inspection Request from: Victoria Beall 3rd floor, south side rooms anop ok
|
Electrical Rough-In | 2/2/2007 | 2/5/2007 | 2/5/2007 | A | PART |
Bob Reichert
|
|
|
JASON; Phone #: ###-#### Internet Inspection Request from: Victoria Beall ok to cover high clg in lobby area anop
|
Electrical Rough-In | 1/31/2007 | 2/1/2007 | 2/1/2007 | A | PART |
Bob Reichert
|
|
|
jason; Phone #: ###-#### Internet Inspection Request from: Victoria Beall lobby area hard lids only ok to cover
|
Final | 1/31/2007 | 2/1/2007 | 2/1/2007 | A | PART |
Bob Reichert
|
|
|
jason; Phone #: ###-#### Internet Inspection Request from: Victoria Beall 4th rooms anop ok for final
|
Electrical Rough-In | 1/31/2007 | 1/31/2007 | 1/31/2007 | P | NR |
Bob Reichert
|
|
|
jason; Phone #: ###-#### Internet Inspection Request from: Victoria Beall met contr, temp lites still up, fa not done, speakers not done
|
Final | 1/29/2007 | 1/30/2007 | 1/30/2007 | A | PART |
Bob Reichert
|
|
|
Jason; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt 4th floor, south side rooms ok
|
Electrical Rough-In | 1/25/2007 | 1/25/2007 | 1/25/2007 | P | PART |
Jack Frank
|
|
|
JASON; Phone #: ###-#### Internet Inspection Request from: Victoria Beall r/i anop 1 office soffit ,1 office hard ceiling
|
Electrical Rough-In | 1/16/2007 | 1/16/2007 | 1/16/2007 | P | PART |
Bob Reichert
|
|
|
Jason; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt hard lid 1st fl corridor anop ok to cover, upper floors dropped ceilings nr
|
Electrical Rough-In | 1/3/2007 | 1/4/2007 | 1/4/2007 | A | PART |
Bob Reichert
|
|
|
jason; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles lobby and north walls anop ok to cover
|
Electrical Rough-In | 12/28/2006 | 12/29/2006 | 12/29/2006 | A | PART |
Bob Reichert
|
|
|
jason; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ric anop north of lobby walls only ok to cover
|
Permanent Service | 12/21/2006 | 12/22/2006 | 12/22/2006 | A | PASS |
Bob Reichert
|
|
|
jason; Phone #: ###-#### Internet Inspection Request from: Sherri Bennett p/s u/g n ok
|
Electrical Rough-In | 12/21/2006 | 12/21/2006 | 12/21/2006 | P | PART |
Mike Kinnear
|
|
|
jason ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok cover walls & hard lid ceiling anop
|
Electrical Rough-In | 12/18/2006 | 12/18/2006 | 12/18/2006 | P | PART |
Pat Lass
|
|
|
jason; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles rooms off east hallway ok
|
Electrical Rough-In | 12/15/2006 | 12/15/2006 | 12/15/2006 | P | PART |
Jack Frank
|
|
|
Jason; Phone #: ###-#### Internet Inspection Request from: Sherri Bennett walls in kit.
|
Electrical Rough-In | 12/5/2006 | 12/5/2006 | 12/5/2006 | P | PART |
Bob Reichert
|
|
|
jason ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith 1st floor guest rooms anop walls only ok to cover
|
Conference | 12/4/2006 | 12/4/2006 | 12/4/2006 | P | DONE |
Bob Reichert
|
|
|
jason; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles Furniture is coming and power won't be turned on for a couple of weeks, so they are asking about placing furniture in completed rooms if kept 3' away from recpts so final inspection can be done. Agreed ok by 370.
|
Electrical Rough-In | 10/2/2006 | 10/2/2006 | 10/2/2006 | P | PASS |
Jack Frank
|
|
|
jason; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles 2nd anop
|
Electrical Rough-In | 9/28/2006 | 9/28/2006 | 9/29/2006 | P | FAIL |
Jack Frank
|
|
|
jason; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr. called needs mail plates and 11/4"
|
Electrical Rough-In | 9/25/2006 | 9/25/2006 | 9/25/2006 | P | DONE |
Jack Frank
|
|
|
jason; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles done 09-22-06
|
Electrical Rough-In | 9/22/2006 | 9/22/2006 | 9/22/2006 | P | PART |
Jack Frank
|
|
|
jason; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles 2nd floor long wing walls ceiling for rms
|
Electrical Rough-In | 9/11/2006 | 9/11/2006 | 9/11/2006 | P | PART |
Jack Frank
|
|
|
jason; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles anop 3rd floor
|
Electrical Rough-In | 9/7/2006 | 9/7/2006 | 9/7/2006 | P | PART |
Jack Frank
|
|
|
jason; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles walls ceilings anop 3rd floor
|
Electrical Rough-In | 8/31/2006 | 9/1/2006 | 9/1/2006 | A | PART |
Jack Frank
|
|
|
jason; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie E grid anop pool and spa
|
Electrical Rough-In | 8/30/2006 | 8/31/2006 | 8/31/2006 | A | CANC |
Jack Frank
|
|
|
jason - pool grounding; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley contr called and canceled inspection
|
Electrical Rough-In | 8/29/2006 | 8/30/2006 | 8/30/2006 | A | PART |
Bob Reichert
|
|
|
jason; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley 4th floor halls, walls only ok to cover anop
|
Electrical Rough-In | 8/23/2006 | 8/23/2006 | 8/23/2006 | P | PART |
Mike Kinnear
|
|
|
jason; Phone #: ###-#### Internet Inspection Request from: Barbara Stitt ok cover room 4th floor west wing anop
|
Electrical Rough-In | 8/18/2006 | 8/18/2006 | 8/18/2006 | P | PART |
Jack Frank
|
|
|
jason; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley 4th floor long wing room walls and ceiling no corridor walls ,or ceilings and no bath rm ceilings
|
Electrical Rough-In | 8/17/2006 | 8/17/2006 | 8/17/2006 | P | NR |
Jack Frank
|
|
|
jason; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley 300.4 nail plates and 11/4", 330.30 (B) strap mc within 12" boxes, 310.15B deration for mc, or spacing for cables
|
Electrical Rough-In | 3/13/2006 | 3/13/2006 | 3/13/2006 | P | PASS |
Mike Kinnear
|
|
|
pool bonding -jason ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ok cover pool & spa bonding only
|
Electrical Rough-In | 3/6/2006 | 3/6/2006 | 3/6/2006 | P | PART |
Jack Frank
|
|
|
JASON - ###-#### - NOTE: UNDERGROUND ok pole lights, phone, catv
|
Rough-In Permanent Service | 1/3/2006 | 1/4/2006 | 1/4/2006 | A | PART |
Jack Frank
|
|
|
DAN nOTE: UNDERGROUND; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles u/g feeders, and phone, catv only
|
Electrical Rough-In | 12/1/2005 | 12/1/2005 | 12/1/2005 | P | PASS |
Mike Kinnear
|
|
|
Contact is Dan. Please inspect UFER grounding system only.; Phone #: ###-#### Internet Inspection Request from: David Bonner ok cover concrete encased electrode on west side of building
|
Owner Supplied Equipment | | | 12/1/2005 | | |
|
|
|
|
Application received | | | 12/1/2005 | | DONE |
|
|
|
This permit was created on the web by David Bonner
|