Final | 5/29/2018 | 5/30/2018 | 5/30/2018 | P | PASS |
Tom Saunders
|
|
|
Lynn Phone #: ###-####...corrections made...ok to final
|
Final | 5/24/2018 | 5/29/2018 | 5/29/2018 | P | FAIL |
Tom Saunders
|
|
|
Lynn Phone #: ###-####-please call with a meet time... 1.. light switch and fixture need added at each exterior door exiting grade level 2..romex shall be protected from physical damge..horizontal runs under 8' 3..w/p proof outlet cover needs fixed 4...outlets under panel need removed or wired correctly
|
Change Status to I | | | 5/24/2018 | | DONE |
|
|
|
as per Daryl D. change status to ISS
|
Permanent Service | 12/1/2005 | 12/2/2005 | 12/2/2005 | A | PART |
Jack Frank
|
|
|
lynn; Phone #: ###-#### Internet Inspection Request from: Barbara Moore p/s u/g new ok only cor. posted for r/i and final 210.70 switch and fixtures required for outside exit doors, 300.4 and 334.15 needs 11/4", and run exposed cables so protected as code noted states 312. 5 conn for GEC
|
Application received | | | 12/1/2005 | | |
|
|
|
|
Issue permit | | | 12/1/2005 | | DONE |
|
|
|
|