Final | 2/22/2006 | 2/23/2006 | 2/23/2006 | A | PASS |
Pat Lass
|
|
|
Aaron; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong
|
Rough-In Permanent Service | 12/6/2005 | 12/7/2005 | 12/7/2005 | A | PASS |
Jack Frank
|
|
|
bob; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles r/i ok p/s u/g new ok
|
Electrical Rough-In | 12/6/2005 | 12/7/2005 | 12/7/2005 | A | CANC |
Jim Schmer
|
|
|
bob; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles was put into computer twice by mistake. JMS
|
Rough-In Permanent Service | 12/5/2005 | 12/6/2005 | 12/6/2005 | A | FAIL |
Bob Reichert
|
|
|
bob ###-#### called, left message, left corr notice,312.5 abrasion protection shall be provided for all conductors entering enclosure,300.4(D)nm cable shall be 1 1/4" from edge of framing member,314.16 boxes shall be of sufficient size to provide free space for all enclosed conductors,garage, 314.19 boxes shall be flush to completely cover front light
|
Issue permit | | | 12/5/2005 | | DONE |
|
|
|
|
Application received | | | 12/5/2005 | | |
|
|
|
|