Second Notice ELE | 12/28/2005 | 12/28/2005 | 12/29/2005 | | DONE |
|
|
|
This permit finaled on the web by Dana Moyer
|
First Notice | 12/15/2005 | 12/15/2005 | 12/28/2005 | | DONE |
Jack Frank
|
|
|
|
Final | 12/14/2005 | 12/15/2005 | 12/15/2005 | A | PASS |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Dana Moyer
|
Final | 12/14/2005 | 12/14/2005 | 12/14/2005 | P | NR |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Dana Moyer
|
Permanent Service | 12/7/2005 | 12/14/2005 | 12/14/2005 | P | PASS |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Dana Moyer p/s u/g rec. ok
|
Permanent Service | 12/6/2005 | 12/7/2005 | 12/7/2005 | A | FAIL |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Dana Moyer cor. fee due, met contractor, 250.92(A)(3) shall bond both ends where GEC is in metal 312,5 needs conn for GEC314.28 needs bigger J box bottom of p/s,310.15(B)(6) needs 2/0 to each meter base300.10 bond bushings where RE washers are used, 250.66 all GEC abd main bonds shall be #2 copper 250.148 splice all equip grds together and tap box top of p/s110.3(A) shall replace damaged bus from arcing effects right side p/s panel replace all splices and terminations where wire is ringed from stripping
|
Stop Work/Reinspection Fee | 12/7/2005 | 12/7/2005 | 12/7/2005 | A | DONE |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Dana Moyer reinspection fee due per JSchmer
|
Permanent Service | 12/6/2005 | 12/6/2005 | 12/6/2005 | P | FAIL |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Dana Moyer wrong address and corrections
|
Application received | | | 12/5/2005 | | DONE |
|
|
|
This permit was created on the web by Dana Moyer
|