Final | 4/21/2006 | 4/21/2006 | 4/21/2006 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: TJ Sturges corr made, ok to final
|
Final | 4/19/2006 | 4/19/2006 | 4/19/2006 | P | FAIL |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: TJ Sturges corr. called 314.16 box fill all boxes island counter, 210.8 needs gfci MB sinks,410.8 install fixture with required clearence or remove all wiring understairs closet, 334.15 protect all exposed wiring, and install conn on all flex both ends island counter, 210.52(A) outlet spacing nupstairs bed rm by window seat/shelves, 406.4 recepts loose in boxes and not flush with plates, panel not labeled correctly schedule does not match branch circuits
|
Electrical Rough-In | 1/10/2006 | 1/11/2006 | 1/11/2006 | A | PASS |
Pat Lass
|
|
|
###-#### Pat please do this asap, it was scheduled online and did not get comfirmed. Please call me if you have questions Thanks Rita. Nicole at Powerbound is your contact ###-#### or Corrie R/I Ok P/S U/G N Ok
|
Application received | | | 12/6/2005 | | DONE |
|
|
|
This permit was created on the web by Corrie Hall
|