Third Notice | | 6/15/2006 | 6/15/2006 | | DONE |
|
|
|
|
Second Notice ELE | 4/26/2006 | 4/26/2006 | 5/17/2006 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice | 4/11/2006 | 4/11/2006 | 4/26/2006 | | DONE |
Bob Reichert
|
|
|
|
Final | 4/10/2006 | 4/11/2006 | 4/11/2006 | A | PASS |
Bob Reichert
|
|
|
Re-inspect for final on pole lights.; Phone #: ###-#### Internet Inspection Request from: todd hall corr made, ok to final, no card to sign
|
Final | 4/7/2006 | 4/10/2006 | 4/10/2006 | A | FAIL |
Bob Reichert
|
|
|
INSPECTION FOR EXTERIOR PARKING LOT LIGHTING (POLE LIGHTS); Phone #: ###-#### Internet Inspection Request from: todd hall called contr, 250.86 poles shall be grounded, did not leave corr notice, told contr to recall when done.
|
Final | 3/30/2006 | 3/30/2006 | 3/30/2006 | P | PART |
Bob Reichert
|
|
|
Final inspect for building only, inspect of remaining items and for items on correction notice. Customer would like CofO for building. Pole lights yet to come. Please call Todd with results. ###-####; Phone #: ###-#### Internet Inspection Request from: todd hall t/o card signed by 336, called left message that we will final later
|
Electrical Rough-In | 3/20/2006 | 3/21/2006 | 3/21/2006 | A | PASS |
Bob Reichert
|
|
|
Todd -- call 1st before insp; prefer 11:00 AM; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong north side drive ok to cover, corrections made
|
Electrical Rough-In | 3/20/2006 | 3/20/2006 | 3/20/2006 | P | NR |
Bob Reichert
|
|
|
Todd -- underground conduit for north end of property; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong called contr, u/g not dug deep enough yet
|
Electrical Rough-In | 3/16/2006 | 3/16/2006 | 3/16/2006 | P | PART |
Bob Reichert
|
|
|
Todd -- reinspection for underground; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong called contr, left message, said east part of driveway ok to cover, but north part still not deep enough. Left "cover ok" sticker on panel. left corr notice posted
|
Final | 3/14/2006 | 3/15/2006 | 3/15/2006 | A | PART |
Pat Lass
|
|
|
Re-inspect for final on building only. Pole lights and sign to be finished when pole lights arrive in approximately one week. Customer would like to move in and begin serving coffee soon.Please call if any questions.; Phone #: ###-#### Internet Inspection Request from: todd hall I signed T/O. directory and underground still not corrected.
|
Final | 3/13/2006 | 3/14/2006 | 3/14/2006 | A | FAIL |
Bob Reichert
|
|
|
please look at trench work also///Phone #: ###-#### Internet Inspection Request from: todd hall called contr, left corr notice,210.63, shall provide 125 v single phase recpt (gfci) for rooftop, 300.5 u/g shall be 24" under drive, 110.3(B) gfci shall operate,408.4 panel sched shall be complete
|
Electrical Rough-In | 3/6/2006 | 3/7/2006 | 3/7/2006 | A | PART |
Pat Lass
|
|
|
Inspect for site light pole bases.; Phone #: ###-#### Internet Inspection Request from: todd hall 2 pole bases ok
|
Permanent Service | 2/24/2006 | 2/24/2006 | 2/24/2006 | P | PASS |
Bob Reichert
|
|
|
re-inspect for perm service. Bob, please inspect asap as per our conversation this am. Please call me as soon as you have an idea when you can inspect so I can call IDPCO to let them know when to re-connect. Thank you.; Phone #: ###-#### Internet Inspection Request from: todd hall p/s reconnect o/h ok
|
Permanent Service | 2/23/2006 | 2/23/2006 | 2/23/2006 | P | NR |
Bob Reichert
|
|
|
Inspection for perm service. Meter can on pole. Please inspect after 2:00pm and before 3:30pm if possible. IDPCO can re-connect at about 4-4:30pm. Please call if any schedule issues.; Phone #: ###-#### Internet Inspection Request from: todd hall contr way behind and told him to re-call for inspection
|
Electrical Rough-In | 1/19/2006 | 1/19/2006 | 1/19/2006 | P | PASS |
Jim Schmer
|
|
|
re-inspect for rough-in. Please look at the UFER installation at the drain out along the South wall; Phone #: ###-#### Internet Inspection Request from: todd hall ufer ok, tied to rebar by drain, r/i ok correction made jms
|
Electrical Rough-In | 1/18/2006 | 1/19/2006 | 1/19/2006 | A | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: todd hall met elect, left corr notice, 300.4(A) & (D) 1 1/4" for holes and mc casble shall be maintained, 110.12(C) there shall be no damaged parts, 330.30(B) mc cable shall be strapped within 12" of box
|
Electrical Rough-In | 1/5/2006 | 1/5/2006 | 1/5/2006 | P | PART |
Bob Reichert
|
|
|
underground- todd; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie u/g fom bldg east to light pole, and so toward chinden ok to cover
|
Electrical Rough-In | 12/20/2005 | 12/20/2005 | 12/20/2005 | P | CANC |
Bob Reichert
|
|
|
todd Note: ufier; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles cancelled to concrete
|
Override - Parcel Holds | 1/1/1900 | 1/1/1900 | 12/20/2005 | | |
|
|
|
|
Electrical Rough-In | 12/12/2005 | 12/13/2005 | 12/13/2005 | P | PART |
Bob Reichert
|
|
|
###-#### - todd Hall Note: underground u/g under bldg only ok to cover, need to see rest later
|
Override - Parcel Holds | | | 12/12/2005 | | |
|
|
|
|
Issue permit | | | 12/12/2005 | | DONE |
|
|
|
|
Application received | | | 12/12/2005 | | |
|
|
|
|
Override - Parcel Holds | | | 12/12/2005 | | |
|
|
|
|