Final | 4/14/2006 | 4/14/2006 | 4/14/2006 | P | PASS |
Jack Frank
|
|
|
ken; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok
|
Electrical Rough-In | 1/9/2006 | 1/10/2006 | 1/10/2006 | A | PASS |
Jack Frank
|
|
|
KEN nOTE: PLEASE CALL 1/2 HR IF PR0BLEM; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie r/i ok
|
Electrical Rough-In | 1/9/2006 | 1/9/2006 | 1/10/2006 | P | FAIL |
Jack Frank
|
|
|
please call prior to inspection///ken; Phone #: ###-#### Internet Inspection Request from: Barbara Moore cor. not made terminate GEC to p/s not subpanel
|
Electrical Rough-In | 1/4/2006 | 1/4/2006 | 1/4/2006 | P | FAIL |
Jack Frank
|
|
|
ken ; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles cor. do not cover, called 210.52(A&B) needs out in new bedrm 2ft wall, all outlets in din rm shall be kit circuit, 210.52(C) countertop outlet spacing, 314.17 replace boxes with broken clamps, 250.148 splice all equip grds together at boxes, 250.52(A)(1) grd u/g water pipe 5ft300.10&12 4 locknuts for rigid nipple p/s subpanel, 300.4(A)(1)(D) all locations, 110.12 seal all unused KOs no tin can lids to be used 230.28 guy kit mast,312.5 conn for GEC, remove GEC from subpanel
|
Application received | | | 12/15/2005 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 12/15/2005 | | DONE |
|
|
|
|