Final | 2/10/2006 | 2/13/2006 | 2/13/2006 | P | PASS |
Bob Reichert
|
|
|
call for garage code///nicole ###-#### or cody; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa corrections made, ok to final
|
Final | 2/10/2006 | 2/10/2006 | 2/10/2006 | P | FAIL |
Bob Reichert
|
|
|
NICHOLE OR CODY ###-#### NOTE: PLEASE CALL CODE NUMBER; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called contr, left corr notice, 406.4 recpts shall be securely fastened in place(laundry and garage gfci), 406.5 recpt faceplates shall completely cover opening (microwave), 210.52(B)(3) & 408.4 kitchen small appliance branch circuits shall be minimum 2 and so identified on circuit directory, 410.5 luminaires shall be installed with guards so that combustible material is not subjected to temperatures in excess of 90 c (194 f)
|
Electrical Rough-In | 12/23/2005 | 12/27/2005 | 12/27/2005 | A | PASS |
Bob Reichert
|
|
|
cody or ###-#### steve ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie corr made, ric ok, p/s u/g n ok
|
Rough-In Permanent Service | 12/21/2005 | 12/22/2005 | 12/22/2005 | A | FAIL |
Jack Frank
|
|
|
nicole; Phone #: ###-#### Internet Inspection Request from: Barbara Moore cor. called left message, needs 11/4" and nail plates, 110.3,314.17,110.12 replace all outside boxes with broken out factory clamps, replace all boxes with extra KOs broken out, 334.24 all cables shall have a radius of not less than 5 times the diameter
|
Application received | | | 12/19/2005 | | DONE |
|
|
|
This permit was created on the web by Corrie Hall
|