Second Notice ELE | 1/25/2006 | 1/25/2006 | 2/6/2006 | | DONE |
|
|
|
First Notice has not been responded to.
|
Second Notice ELE | 1/25/2006 | 1/25/2006 | 2/6/2006 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice | 1/6/2006 | 1/6/2006 | 1/25/2006 | | DONE |
Pat Lass
|
|
|
|
First Notice | 1/6/2006 | 1/6/2006 | 1/25/2006 | | DONE |
Pat Lass
|
|
|
|
Final | 1/5/2006 | 1/6/2006 | 1/6/2006 | A | PASS |
Pat Lass
|
|
|
Scheduled by a contractor via Hello! on 1/5/2006 at 10:04:12 PM. Contact: ###-####.
|
Temporary Service | 1/6/2006 | 1/6/2006 | 1/6/2006 | P | PASS |
Pat Lass
|
|
|
Scheduled by a contractor via Hello! on 1/5/2006 at 10:04:12 PM. Contact: ###-####. T/S U/G Ok
|
Final | 1/3/2006 | 1/4/2006 | 1/4/2006 | A | FAIL |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 1/3/2006 at 12:46:42 PM. Contact: ###-####. called contr, left corr notice,250.53(G) electrode shall be flush with or below ground, at least 8' shall be in contact with soil
|
Temporary Service | 12/28/2005 | 12/29/2005 | 12/29/2005 | A | FAIL |
Bob Reichert
|
|
|
###-#### - jerry called contr, left message, fee due, 250.24 gec shall be connected,110.3 shall provide deadfront screw, 310.7 direct buried cinductors shall be identified for such use
|
Stop Work/Reinspection Fee | 12/29/2005 | 12/29/2005 | 12/29/2005 | P | FAIL |
Bob Reichert
|
|
|
see failed inspection
|
Application received | | | 12/21/2005 | | |
|
|
|
|
Issue permit | | | 12/21/2005 | | DONE |
|
|
|
|