Final | 6/30/2006 | 7/5/2006 | 7/5/2006 | A | CANC |
Jack Frank
|
|
|
john; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
|
Final | 7/3/2006 | 7/3/2006 | 7/3/2006 | P | PASS |
Mike Kinnear
|
|
|
john; Phone #: ###-#### Note: Please call 1/2 hr prior Internet Inspection Request from: Cathy Chiles corrections made ok final
|
Final | 6/22/2006 | 6/22/2006 | 6/22/2006 | P | FAIL |
Jack Frank
|
|
|
tracy - call 1/2 hr prior for access; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley 250.104 (A)(1) and T250.66 shall bond water system with #4 copper, and remove it from subpanel, 210.8(A)(5) gfci for recepts unfinished basement, 334.15 protect romex in unfinished basement where horizontal runs are called
|
Electrical Rough-In | 6/9/2006 | 6/9/2006 | 6/9/2006 | P | PASS |
Jack Frank
|
|
|
john call prior to insp for access; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ok
|
(F) Reprint permit | | | 6/9/2006 | | DONE |
|
|
|
|
Electrical Rough-In | 6/1/2006 | 6/2/2006 | 6/2/2006 | P | FAIL |
Jack Frank
|
|
|
John, early afternoon if possible; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt met with owner, needs some nail plates still, and correct box fill told owner to check all location 2 gag cutins, old steel 2 gang bottom of stairs, and replace 2 gang with broken clamps funace rm
|
Electrical Rough-In | 5/18/2006 | 5/19/2006 | 5/19/2006 | P | NR |
Pat Lass
|
|
|
john Note: please call 1/2 hr prior; Phone #: ###-#### Internet Inspection Request from: Cathy Chileshad conf about general requirements
|
Permanent Service | 2/7/2006 | 2/8/2006 | 2/8/2006 | A | PASS |
Bob Reichert
|
|
|
please call 30 min prior to meet you//tracy; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa talked to owner, told to provide abrasion protection for gec in sub-panel, and add bond bushing to service panel, put cover on subpanel prior to energizng panel. Told owner to call for ri before cover. p/s o/h n ok
|
Permanent Service | 1/24/2006 | 1/24/2006 | 1/24/2006 | P | FAIL |
Bob Reichert
|
|
|
please call 30 min prior to meet you///tracy; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa met owner, left corr notice, 250.104(A) metal water piping system shall be bonded to service enclosure, 230.28 service mast shall be supported by brace or guy kit, 408.38 service panel shall be deadfront, BCC no violations shall be retained, example range and dryer shall be 4 wire wired
|
Permanent Service | 1/19/2006 | 1/20/2006 | 1/20/2006 | A | CANC |
Bob Reichert
|
|
|
Traci -- call right before insp on site; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong cust asked to cancel.
|
Conference | 12/29/2005 | 1/3/2006 | 1/3/2006 | P | NH |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 12/29/2005 at 3:17:55 PM. Contact: ###-####. notice posted called left # message
|
Application received | | | 12/29/2005 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 12/29/2005 | | |
|
|
|
|