Permit Information
Permit NumberELE05-04648
StatusFinaled
Name JOHN COLTON ELECTRIC
Site Address 1802 N LIBERTY RD
Project Name 
Customer Number 
ePlanReview 
Description
Added 5 rooms per home owner///6/9/06 BAS-changed to Electrical Contractor C-26686 6/29/2006 cmc
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final6/30/20067/5/20067/5/2006ACANC
DetailsJack Frank
john; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
Final7/3/20067/3/20067/3/2006PPASS
DetailsMike Kinnear
john; Phone #: ###-#### Note: Please call 1/2 hr prior Internet Inspection Request from: Cathy Chiles corrections made ok final
Final6/22/20066/22/20066/22/2006PFAIL
DetailsJack Frank
tracy - call 1/2 hr prior for access; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley 250.104 (A)(1) and T250.66 shall bond water system with #4 copper, and remove it from subpanel, 210.8(A)(5) gfci for recepts unfinished basement, 334.15 protect romex in unfinished basement where horizontal runs are called
Electrical Rough-In6/9/20066/9/20066/9/2006PPASS
DetailsJack Frank
john call prior to insp for access; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ok
(F) Reprint permit  6/9/2006 DONE
Electrical Rough-In6/1/20066/2/20066/2/2006PFAIL
DetailsJack Frank
John, early afternoon if possible; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt met with owner, needs some nail plates still, and correct box fill told owner to check all location 2 gag cutins, old steel 2 gang bottom of stairs, and replace 2 gang with broken clamps funace rm
Electrical Rough-In5/18/20065/19/20065/19/2006PNR
DetailsPat Lass
john Note: please call 1/2 hr prior; Phone #: ###-#### Internet Inspection Request from: Cathy Chileshad conf about general requirements
Permanent Service2/7/20062/8/20062/8/2006APASS
DetailsBob Reichert
please call 30 min prior to meet you//tracy; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa talked to owner, told to provide abrasion protection for gec in sub-panel, and add bond bushing to service panel, put cover on subpanel prior to energizng panel. Told owner to call for ri before cover. p/s o/h n ok
Permanent Service1/24/20061/24/20061/24/2006PFAIL
DetailsBob Reichert
please call 30 min prior to meet you///tracy; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa met owner, left corr notice, 250.104(A) metal water piping system shall be bonded to service enclosure, 230.28 service mast shall be supported by brace or guy kit, 408.38 service panel shall be deadfront, BCC no violations shall be retained, example range and dryer shall be 4 wire wired
Permanent Service1/19/20061/20/20061/20/2006ACANC
DetailsBob Reichert
Traci -- call right before insp on site; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong cust asked to cancel.
Conference12/29/20051/3/20061/3/2006PNH
DetailsJack Frank
Scheduled by a contractor via Hello! on 12/29/2005 at 3:17:55 PM. Contact: ###-####. notice posted called left # message
Application received  12/29/2005  
Issue PAID IN FULL permit  12/29/2005