Final | 3/10/2006 | 3/13/2006 | 3/13/2006 | A | PASS |
Bob Reichert
|
|
|
Alan; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong called contr, left survey, 408.4 circuit directory shall be complete, 314.25 recpt in garage shall have faceplate, 210.52(A) library room shall have additional recpt
|
Electrical Rough-In | 12/30/2005 | 1/3/2006 | 1/3/2006 | P | DONE |
Jack Frank
|
|
|
###-#### - allen
|
Permanent Service | 1/3/2006 | 1/3/2006 | 1/3/2006 | A | PASS |
Jack Frank
|
|
|
###-#### - allen p/s u/g new ok
|
Rough-In Permanent Service | 1/3/2006 | 1/3/2006 | 1/3/2006 | A | PASS |
Jack Frank
|
|
|
r/i ok p/s u/g new ok
|
Rough-In Permanent Service | 12/29/2005 | 12/30/2005 | 12/30/2005 | A | FAIL |
Jack Frank
|
|
|
allen ###-#### cor. posted called left message 210.52(A) required outlet spacing liv rm common wall with kit, needs to update permit for 16 rms, and a seperate permit for outbuilding garage, 1 p/s 1 rm
|
Issue permit | | | 12/29/2005 | | DONE |
|
|
|
|
Application received | | | 12/29/2005 | | |
|
|
|
|