Final | 4/21/2006 | 4/21/2006 | 4/21/2006 | A | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 4/21/2006 at 7:22:14 AM. Contact: ###-####. corr made, ok to final
|
Final | 4/19/2006 | 4/20/2006 | 4/20/2006 | A | FAIL |
Bob Reichert
|
|
|
MIKE; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called contr, left corr notice, 422.31(B) shall provide bkr lo for dishwasher, 430.107 motor disconnect for jetted tub shall be readily accessible, 406.5 recpt faceplates shall seat against finished surface, front room, kitchen island shall have faceplates installed, 110.3 mud room recpt shall operate, washer recpt shows bad neutral
|
Rough-In Permanent Service | 1/9/2006 | 1/10/2006 | 1/10/2006 | A | PASS |
Bob Reichert
|
|
|
eric ###-#### ric ok, p/s u/g n ok
|
Issue & PRINT permit | | | 1/9/2006 | | DONE |
|
|
|
|
Application received | | | 1/9/2006 | | |
|
|
|
|