Final | 3/28/2006 | 3/29/2006 | 3/29/2006 | A | PASS |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 3/28/2006 at 7:02:37 PM. Contact: ###-####. ok water heating equip replace with gas water heater called needs to grd 2 metal boxes in island counter
|
Final | 3/24/2006 | 3/24/2006 | 3/24/2006 | P | FAIL |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 3/24/2006 at 6:07:41 AM. Contact: ###-####. corr. posted called 110.26(F)(1) required space sub panel for hot water system laundry rm, 110.3 shall follow all manufactures instructions for hot water system min #6 wire, min. breaker 60 amp,220.40 shall calc service and feeder to hot water system sub panel both of them too small , 250.118 (5) both flexes at hot water system need equip grds
|
Rough-In Permanent Service | 1/9/2006 | 1/10/2006 | 1/10/2006 | A | PASS |
Mike Kinnear
|
|
|
Brannon; Phone #: ###-#### Internet Inspection Request from: Rowdy Monroe ok cover ri p/s u/g n ok
|
Application received | | | 1/9/2006 | | DONE |
|
|
|
This permit was created on the web by Rowdy Monroe
|