Electrical Rough-In | 1/24/2006 | 1/24/2006 | 1/24/2006 | P | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 1/24/2006 at 9:17:09 AM. Contact: ###-####. talked to contr, corrections made, will change breakers by final, he didn't do other work in house, ric ok
|
Electrical Rough-In | 1/10/2006 | 1/10/2006 | 1/10/2006 | P | FAIL |
Jack Frank
|
|
|
zane ###-#### cor. do not cover called, BCC no violations retained needs clearence for p/s use manufactures breakers, #12 & #14 mixed watch for overcurrent prtion 3 way stairs basement, 300.4 nail plates 11/4"" 314.16 box fill 110.3 replace all damaged boxes ( holes drilled in the side, broken factory clamps, 314.43 no screws in plastic boxes, COW
|
Application received | | | 1/10/2006 | | |
|
|
|
|
Issue permit | | | 1/10/2006 | | DONE |
|
|
|
|