Temporary Service | 1/11/2006 | 1/12/2006 | 1/12/2006 | A | PASS |
Bob Reichert
|
|
|
brian --re-insp; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie corrections made, t/s u/g n ok
|
Temporary Service | 1/11/2006 | 1/11/2006 | 1/11/2006 | P | FAIL |
Bob Reichert
|
|
|
brian -###-#### called contr, left corr notice, 250.53(G) rod electrode shall be such that upper end is flush with or below gnd, 250.24(A)(1) gndg electrode conductor shall be connected to gnded conductor bus,110.14(A) connections shall be tight,110.3(B) equipment shall be installed per instructions,all screws provided, 250.52(A)(5)(b) steel electrode shall be at least 5/8" diameter, fee due
|
Issue & PRINT permit | | | 1/11/2006 | | DONE |
|
|
|
|
Application received | | | 1/11/2006 | | |
|
|
|
|