Final | 7/24/2007 | 7/26/2007 | 7/26/2007 | P | PASS |
Bob Reichert
|
|
|
Final - pls call Jim w/Doherty @ ###-#### 30min prior so that he can meet the inspector to walk through - Jim will be 2 houses down from there. Scheduled by Heather w/Doherty Phone #: ###-#### Internet Inspection Request from: Heather Packer met contr, ok to final
|
Permanent Service | 1/18/2006 | 1/18/2006 | 1/18/2006 | P | PASS |
Jack Frank
|
|
|
Call Tim 1/2hr before for access; Phone #: ###-#### Internet Inspection Request from: Heather Packer p/s u/g rec. ok
|
Electrical Rough-In | 1/17/2006 | 1/18/2006 | 1/18/2006 | A | PASS |
Jack Frank
|
|
|
wall cover--pls call Tim 1/2 hr before for access ###-####; Phone #: ###-#### Internet Inspection Request from: Heather Packer ok
|
Permanent Service | 1/16/2006 | 1/17/2006 | 1/17/2006 | A | FAIL |
Jack Frank
|
|
|
Please call 1/2 before for access - Tim ###-####; Phone #: ###-#### Internet Inspection Request from: Heather Packer see r/i notes
|
Electrical Rough-In | 1/16/2006 | 1/17/2006 | 1/17/2006 | A | FAIL |
Jack Frank
|
|
|
Please call 1/2 before for access - Tim ###-####; Phone #: ###-#### Internet Inspection Request from: Heather Packer cor. called 314.16 box fill 300.4 nail plates and 11/4", 250.66 all grds and bond #$, 250. 52(A)(1) or 104(A)(1) grd or bond water system 250.24 (A)(1) all grds and bonds shall terminate at neutral bus, 250.90,92 bond all raceways and nipples at p/s with #4, 250.56 needs 2 grd rods
|
Application received | | | 1/11/2006 | | DONE |
|
|
|
This permit was created on the web by Heather Packer
|