Second Notice ELE | 10/10/2006 | 10/10/2006 | 10/12/2006 | | DONE |
|
|
|
This permit finaled on the web by Jeff Radford
|
First Notice | 9/29/2006 | 9/29/2006 | 10/10/2006 | | DONE |
Bob Reichert
|
|
|
|
Final | 9/28/2006 | 9/29/2006 | 9/29/2006 | A | PASS |
Bob Reichert
|
|
|
mike; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corrections made, equipment labelled, ok to final, signed card
|
ELE-Aging Inspection | 8/28/2006 | 8/28/2006 | 8/29/2006 | | DONE |
Bob Reichert
|
|
|
called, they may want to evaluate 2 jobs for same owner, elect will check
|
Final | 6/27/2006 | 6/28/2006 | 6/28/2006 | P | CANC |
Bob Reichert
|
|
|
mike; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles see conf
|
Conference | 6/28/2006 | 6/28/2006 | 6/28/2006 | P | DONE |
Bob Reichert
|
|
|
mike; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles met contr, air comp supplier, gen to discuss listing for air comp
|
Final | 6/20/2006 | 6/20/2006 | 6/20/2006 | P | FAIL |
Bob Reichert
|
|
|
BCC 4-05-33(A)(B) equipment shall be listed and labelled by a nationally recognized testing lab (air comp)
|
Final | 5/25/2006 | 5/25/2006 | 5/26/2006 | P | PART |
Bob Reichert
|
|
|
mike ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie looked at recpts,they need to wire hot water heater, air comp, finish strapping conduit, install counter in front, install approved egress lights, ensure listing for paint boothes. I wouldn't sign t/o, said to finish and call for final inspection. Posted correction notice 5-26-06. Signed t/o card
|
Electrical Rough-In | 5/11/2006 | 5/11/2006 | 5/11/2006 | P | PART |
Bob Reichert
|
|
|
mike Note: ceiling; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok to cover ceilings, office areas only
|
Permanent Service | 5/8/2006 | 5/8/2006 | 5/8/2006 | P | PASS |
Bob Reichert
|
|
|
mike; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles p/s u/g n ok
|
Permanent Service | 5/2/2006 | 5/2/2006 | 5/2/2006 | P | FAIL |
Bob Reichert
|
|
|
mike; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles talked w/contr, left corr notice, nec 314.28 (A)(2) pull and junction box shall be sized for angle pulls- not less than 16" opposite wall of 2" conduits
|
Electrical Rough-In | 4/17/2006 | 4/18/2006 | 4/18/2006 | A | PASS |
Bob Reichert
|
|
|
Mike; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong walls and hard lids ok to cover only
|
Conference | 4/18/2006 | 4/18/2006 | 4/18/2006 | A | DONE |
Jack Frank
|
|
|
Mike; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong reviewing prints of classified area , still needs documentation?
|
Electrical Rough-In | 4/10/2006 | 4/10/2006 | 4/10/2006 | P | NR |
Bob Reichert
|
|
|
Mike; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong they received data on air changes, not classification for hazardous area. They called architect, I explained what we need, he said that Electrical engineer should provide the area classification per 500.4.
|
Electrical Rough-In | 4/5/2006 | 4/5/2006 | 4/5/2006 | P | NR |
Bob Reichert
|
|
|
Mike -- for wall; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong they don't have classification areas defined per 500 (4), met with contr and builder and told them that engineer must classify hazardous areas
|
Electrical Rough-In | 4/3/2006 | 4/4/2006 | 4/5/2006 | P | NR |
Bob Reichert
|
|
|
Mike -- wall rough in; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong wrote correction, 500.4(A) all areas designated as hazardous (classified) locations shall be properly documented. This documentation shall be available ffor users.
|
Electrical Rough-In | 3/7/2006 | 3/8/2006 | 3/8/2006 | A | PART |
Jack Frank
|
|
|
Mike -- underground; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong u/g for office area only needs documuntation for repair garage and spray booth areas
|
Electrical Rough-In | 1/13/2006 | 1/13/2006 | 1/13/2006 | P | PASS |
Bob Reichert
|
|
|
underground insp - mike ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie u/g for conduit south side bldg ok to cover.
|
Electrical Rough-In | 1/12/2006 | 1/13/2006 | 1/13/2006 | A | PASS |
Bob Reichert
|
|
|
grounding inspection//mike; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa gec only ok to backfill
|
Electrical Rough-In | 1/12/2006 | 1/12/2006 | 1/12/2006 | P | PASS |
Bob Reichert
|
|
|
THIS IS FOR A UFER INSPECTION - ANY QUESTIONS PLEASE CALL MIKE HICKS; Phone #: ###-#### Internet Inspection Request from: Jeff Radford ok to cover gec, need to see before backfill
|
Electrical Rough-In | 1/11/2006 | 1/12/2006 | 1/12/2006 | A | CANC |
Bob Reichert
|
|
|
ANY QUESTIONS PLEASE CALL MIKE HICKS-THIS IS FOR A UFER INSPECTION; Phone #: ###-#### Internet Inspection Request from: Jeff Radford do in pm
|
Owner Supplied Equipment | | | 1/11/2006 | | |
|
|
|
|
Application received | | | 1/11/2006 | | DONE |
|
|
|
This permit was created on the web by Jeff Radford
|