Second Notice ELE | 12/26/2006 | 12/26/2006 | 1/4/2007 | | DONE |
|
|
|
This permit finaled on the web by Sandee Johnson
|
First Notice | 10/11/2006 | 10/11/2006 | 12/26/2006 | | DONE |
Jack Frank
|
|
|
|
Final | 10/10/2006 | 10/11/2006 | 10/11/2006 | A | PASS |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok card signed
|
Final | 10/3/2006 | 10/3/2006 | 10/3/2006 | P | PART |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Patricia Smith left corr notice from 10/2/06 open, signed t/o card for bldg, told elect to be sure exhaust system not operational
|
Final | 10/2/2006 | 10/2/2006 | 10/2/2006 | P | PART |
Bob Reichert
|
|
|
mike; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok for showroom area only, signed card, left corr notice, nec 514.3(B)(1) fuel dispenser shall provide clearances per table, 511.12 recpts shall be gfci, 511.3(A)(5) wiring shall be 18" above floor or class1, 430.102(B) door opener shall have disconnect, 330.39(B) mc cable shall be secured within 12" of box, BCC 4-05-33(A)&(B) exhaust system shall listed and labelled , check polarity on lifts and complete soffit lighting,NOTE: corrections shall be made in 2 weeks or further action can be taken such as removal of power
|
Electrical Rough-In | 9/13/2006 | 9/13/2006 | 9/13/2006 | P | PASS |
Bob Reichert
|
|
|
mike - ceiling insp; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ok to cover ceiling
|
Electrical Rough-In | 8/23/2006 | 8/24/2006 | 8/24/2006 | A | PART |
Jack Frank
|
|
|
mike - ceiling; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley N W ceiling areas ok
|
Electrical Rough-In | 8/7/2006 | 8/7/2006 | 8/7/2006 | P | PART |
Bob Reichert
|
|
|
mike --ceiling insp ; Phone #: ###-#### Internet Inspection Request from: Marsha ok to cover clgs in 3 office areas
|
Electrical Rough-In | 7/31/2006 | 8/1/2006 | 8/1/2006 | A | PASS |
Bob Reichert
|
|
|
mike - wall ; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley mezz walls ok to cover only
|
Electrical Rough-In | 7/31/2006 | 7/31/2006 | 7/31/2006 | P | PASS |
Jim Schmer
|
|
|
mike ; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley rest of soffett jms
|
Electrical Rough-In | 7/19/2006 | 7/19/2006 | 7/19/2006 | P | PART |
Bob Reichert
|
|
|
mike; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley 1st floor walls and hard ceilings ok to cover, wrote correction notice to bldr/owner NEC article 514 shall apply to motor fuel dispensing facilities as to class 1 locations and wiring thereto, BCC no violations shall be retained
|
Electrical Rough-In | 7/17/2006 | 7/17/2006 | 7/17/2006 | P | PART |
Bob Reichert
|
|
|
mike ; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ok to cover soffits ne outside area, talked about it is ok to put tiles in around fixtures, but we'll see before all tiles go uo, probably 1/2 ceiling at a time, walls will be ready shortly
|
Final | 6/20/2006 | 6/20/2006 | 6/20/2006 | P | CANC |
Bob Reichert
|
|
|
mike; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles wrong permit number
|
Electrical Rough-In | 6/13/2006 | 6/13/2006 | 6/13/2006 | P | PART |
Bob Reichert
|
|
|
mike; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok to cover showroom area hardlids, s & e walls north part of bldg
|
Permanent Service | 5/8/2006 | 5/8/2006 | 5/8/2006 | P | PASS |
Bob Reichert
|
|
|
mike; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles p/s u/g n ok
|
Electrical Rough-In | 5/2/2006 | 5/2/2006 | 5/2/2006 | P | PART |
Bob Reichert
|
|
|
mike - Note: wall; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles walls west end and north soffit ok to cover only
|
Electrical Rough-In | 4/26/2006 | 4/26/2006 | 4/26/2006 | P | PART |
Mike Kinnear
|
|
|
ok cover part ceiling
|
ELE-Aging Inspection | 4/11/2006 | 4/11/2006 | 4/11/2006 | | DONE |
Bob Reichert
|
|
|
looked at job, suc
|
Electrical Rough-In | 2/8/2006 | 2/9/2006 | 2/9/2006 | P | PASS |
Bob Reichert
|
|
|
Mike -- for underground; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong u/g ok for slab
|
Electrical Rough-In | 1/12/2006 | 1/12/2006 | 1/12/2006 | P | PART |
Jack Frank
|
|
|
THIS IS FOR A UFER INSPECTION - ANY QUESTIONS PLEASE CALL MIKE HICKS; Phone #: ###-#### Internet Inspection Request from: Jeff Radford electrode ok for cover
|
Electrical Rough-In | 1/11/2006 | 1/12/2006 | 1/12/2006 | A | CANC |
Bob Reichert
|
|
|
ANY QUESTIONS PLEASE MIKE HICKS-THIS IS FOR A UFER INSPECTION; Phone #: ###-#### Internet Inspection Request from: Jeff Radford do in pm
|
Owner Supplied Equipment | | | 1/11/2006 | | |
|
|
|
|
Application received | | | 1/11/2006 | | DONE |
|
|
|
This permit was created on the web by Jeff Radford
|