Final | 6/22/2006 | 6/22/2006 | 6/22/2006 | A | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 6/22/2006 at 6:15:47 AM. Contact: ###-####. corr made, ok to final. NOTE: basement not sheetrocked, but ric ok and wiring ok since wired as finished basement
|
Final | 6/21/2006 | 6/21/2006 | 6/21/2006 | P | FAIL |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 6/21/2006 at 5:34:37 AM. Contact: ###-####. called, left message, left corr notice, nec 210.52(A) additional recpt shall be added in dr short wall, 210.8(A)(5) basement recpts shall be gfci protected, 314.29 junction boxes shall be accessible(basement heat), 406.4 back recpt shall be securely mounted,BCC no cover shall be done without inspection(basement ceiling for heat for bathroom floors)
|
Final | 6/20/2006 | 6/20/2006 | 6/20/2006 | P | CANC |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 6/20/2006 at 5:57:10 AM. Contact: ###-####. Inspection cancelled from web by: Marsha Smylie
|
Final | 5/26/2006 | 5/30/2006 | 5/30/2006 | A | CANC |
Bob Reichert
|
|
|
This inspection is for the tile/floor heat.; Phone #: ###-#### Internet Inspection Request from: Rowdy Monroe wrong type inspection
|
Electrical Rough-In | 5/26/2006 | 5/26/2006 | 5/26/2006 | P | PASS |
Bob Reichert
|
|
|
ok to cover floor heat, need to check for j-boxes in basement, and 220v on gfci 4 places
|
Rough-In Permanent Service | 1/16/2006 | 1/17/2006 | 1/17/2006 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Rowdy Monroe ric ok, p/s u/g n ok
|
Application received | | | 1/16/2006 | | DONE |
|
|
|
This permit was created on the web by Rowdy Monroe
|