Second Notice ELE | 3/15/2006 | 3/15/2006 | 3/19/2006 | | DONE |
|
|
|
This permit finaled on the web by joe wheeler
|
Second Notice ELE | 3/15/2006 | 3/15/2006 | 3/16/2006 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice | 2/21/2006 | 2/21/2006 | 3/15/2006 | | DONE |
Bob Reichert
|
|
|
|
First Notice | 2/21/2006 | 2/21/2006 | 3/15/2006 | | DONE |
Bob Reichert
|
|
|
|
First Notice | 2/21/2006 | 2/21/2006 | 3/15/2006 | | DONE |
Bob Reichert
|
|
|
|
Final | 2/20/2006 | 2/21/2006 | 2/21/2006 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: joe wheeler ok to final, signed occ card
|
Electrical Rough-In | 2/1/2006 | 2/2/2006 | 2/2/2006 | A | PASS |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: joe wheeler corrections made r/i ok
|
Electrical Rough-In | 2/1/2006 | 2/1/2006 | 2/1/2006 | P | FAIL |
Jack Frank
|
|
|
energy code compliance being changed by engineer will provide as soon as possible; Phone #: ###-#### Internet Inspection Request from: joe corrections not made 1 more created 300.11(C) shall not use cable to secure or support other cables, 330.30 secure cables within 12' of boxes, 300.4 nail pltes and 11/4" inside outside edges of framing members, had Mike Kinnear look at job also Mike found the same violations called
|
Electrical Rough-In | 1/31/2006 | 2/1/2006 | 2/1/2006 | A | FAIL |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: joe wheeler cor. do not cover posted called 300.4 nail plates & 11/4" 330.30 strap MC within 12" of boxes energy code lighting ? had contractor call BLD inspector
|
Electrical Rough-In | 1/29/2006 | 1/30/2006 | 1/30/2006 | P | FAIL |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: joe wheeler cor do not cover posted called, BCC 04.05.31 part (D) all wiring shall be raceway for comm. wiring note sign circuit required also
|
Application received | | | 1/29/2006 | | DONE |
|
|
|
This permit was created on the web by joe wheeler
|