First Notice | 3/6/2006 | 3/6/2006 | 3/24/2006 | | DONE |
William E Thomas
|
|
|
This permit finaled on the web by Kristopher wilson
|
Final | 3/3/2006 | 3/6/2006 | 3/6/2006 | A | PASS |
William E Thomas
|
|
|
Call Steve Ruter ###-####; Phone #: ###-#### x39 Internet Inspection Request from: Kristopher wilson
|
Final | 3/2/2006 | 3/3/2006 | 3/3/2006 | A | PART |
Bob Reichert
|
|
|
Steve Ruter ###-#### Final inspection Boise Hearing and Speech 13176 W. Persimmon Ln; Phone #: ###-#### x39 Internet Inspection Request from: Kristopher wilson called contr, told to complete panel schedule, adjust receptacles so boxes are not loose in wall, and to be sure exhaust fans are installed. rest ok
|
Permanent Service | 2/7/2006 | 2/8/2006 | 2/8/2006 | A | PASS |
Bob Reichert
|
|
|
Please Call Bobby Langner ###-####; Phone #: ###-#### x39 Internet Inspection Request from: Kristopher wilson called contr, corrections made, ric walls and insulated ceiling ok, p/s, exst meter pak, n, ok
|
Permanent Service | 2/6/2006 | 2/7/2006 | 2/7/2006 | A | FAIL |
Bob Reichert
|
|
|
Service Inspection Please call Steve Ruter ###-####; Phone #: ###-#### x39 Internet Inspection Request from: Kristopher wilson called contr, left corr notice, 250.142(B) gnded circuit conductor shall not be used for grounding non-current carrying metal parts of equip,314.28(A)(2) angle pulls shall not be less than 6 times the size of the largest raceway plus the sum of the diameters of all other raceways in the same row on the same side of the box, 517.13(A) patient care areas shall be provided with a ground path for fault current in a cable that qualifies as an equipment grounding return path per 250.118. Took green sticker down.
|
Electrical Rough-In | 2/1/2006 | 2/2/2006 | 2/2/2006 | A | PASS |
Bob Reichert
|
|
|
Rough in walls. Please Call Bobby Langner ###-####; Phone #: ###-#### x39 Internet Inspection Request from: Kristopher wilson ok to cover walls only, need to see for dropped ceiling. Ceiling and walls ok to insulate
|
Electrical Rough-In | 1/31/2006 | 1/31/2006 | 1/31/2006 | P | PART |
Bob Reichert
|
|
|
Rough in cover inspect Please Call Bobby Langner ###-####; Phone #: ###-#### x39 Internet Inspection Request from: Kristopher wilson called contr, interior walls only ok to cover, not exterior or overhead, left stickers,
|
Application received | | | 1/31/2006 | | DONE |
|
|
|
This permit was created on the web by Kristopher wilson
|