Final | 4/2/2007 | 4/3/2007 | 4/3/2007 | A | PASS |
Jack Frank
|
|
|
todd; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok
|
Stop Work/Reinspection Fee | 8/8/2006 | 8/8/2006 | 4/2/2007 | P | PASS |
Jack Frank
|
|
|
Please call before inspection. ; Phone #: ###-#### Internet Inspection Request from: Todd Holbrook reinspection fee due
|
Rough-In Permanent Service | 8/9/2006 | 8/9/2006 | 8/9/2006 | P | PASS |
Jack Frank
|
|
|
###-#### - r/i p/s o/h rec. ok
|
Final | 8/8/2006 | 8/8/2006 | 8/8/2006 | P | NR |
Jack Frank
|
|
|
Please call before inspection. ; Phone #: ###-#### Internet Inspection Request from: Todd Holbrook see added r/i p/s
|
Rough-In Permanent Service | 8/8/2006 | 8/8/2006 | 8/8/2006 | P | FAIL |
Jack Frank
|
|
|
Please call before inspection. ; Phone #: ###-#### Internet Inspection Request from: Todd Holbrook corr. posted called 210.52(A) required outlet spacing 2 ft 6 ft 12 ft, all areas, 314.16 box fill old metal boxes,, 250.56 needs 2 grd rods, 210.52(E) outlet for front and back outdoors, BCC 2" RMC or IMC for mast,, wire a/c , install hinges on p/s cover
|
Rough-In Permanent Service | 8/8/2006 | 8/8/2006 | 8/8/2006 | A | NH |
William E Thomas
|
|
|
pLEASE CALL ME AHEAD OF INSPECTION SO I CAN LET YOU IN. tHANKS jEFF; Phone #: ###-#### Internet Inspection Request from: Todd Holbrook
|
Application received | | | 1/31/2006 | | DONE |
|
|
|
This permit was created on the web by Todd Holbrook
|