Final | 5/8/2006 | 5/9/2006 | 5/9/2006 | A | PASS |
Bob Reichert
|
|
|
Please call if you have problems. Thanks; Phone #: ###-#### Internet Inspection Request from: Shane Vigil ok to final
|
Rough-In Permanent Service | 2/16/2006 | 2/17/2006 | 2/17/2006 | A | PASS |
Bob Reichert
|
|
|
corrections made please call if you have questions, thanks shane ; Phone #: ###-#### Internet Inspection Request from: Shane Vigil corrections made, ric ok, p/s u/g n ok
|
Final | 2/14/2006 | 2/15/2006 | 2/15/2006 | A | CANC |
Bob Reichert
|
|
|
Posted wrong permit number on job ID tag ele06-00037 please call if you have questions.; Phone #: ###-#### Internet Inspection Request from: Shane Vigil see rip
|
Rough-In Permanent Service | 2/15/2006 | 2/15/2006 | 2/15/2006 | A | FAIL |
Bob Reichert
|
|
|
Posted wrong permit number on job ID tag ele06-00037 please call if you have questions.; Phone #: ###-#### Internet Inspection Request from: Shane Vigil called contr left corr notice, 300.4(A) & (C) edge of holes and nm cable shall be 1 1/4" from edge of framing member, 210.52(A)(1) recptacles shall be spaced so that no point along floor line is over 12' from recpt
|
Application received | | | 2/8/2006 | | DONE |
|
|
|
This permit was created on the web by Shane Vigil
|