Final | 5/16/2006 | 5/16/2006 | 5/16/2006 | P | PASS |
Bob Reichert
|
|
|
tim; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called contr, left survey,nec 210.8(A)(3) outdoor recpt shall be gfci protected
|
Rough-In Permanent Service | 2/21/2006 | 2/22/2006 | 2/22/2006 | A | PASS |
Bob Reichert
|
|
|
brandon; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa corrections made, ric ok, p/s u/g n ok
|
Rough-In Permanent Service | 2/21/2006 | 2/21/2006 | 2/21/2006 | P | FAIL |
Bob Reichert
|
|
|
Brandon; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong called contr, left corr notice, 300.4(A) edge of hole shall be 1/14" from edge of framing member, 334.80 when more than 2 nm conductors pass thru hole to be fire-stopped, ampacity shall be adjusted per 310.15(B)(2)(a), 314.20 box shall be flush with combustible material, 334.30 nm cable shall be supported within 12" of box
|
Application received | | | 2/21/2006 | | |
|
|
|
|
Issue & PRINT permit | | | 2/21/2006 | | |
|
|
|
|