Third Notice ELE | 6/7/2006 | 6/7/2006 | 6/22/2006 | | DONE |
|
|
|
Second Notice has not been responded to.
|
Second Notice ELE | 4/26/2006 | 4/26/2006 | 6/7/2006 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice | 4/4/2006 | 4/4/2006 | 4/26/2006 | | DONE |
William E Thomas
|
|
|
|
Final | 4/4/2006 | 4/4/2006 | 4/4/2006 | P | PASS |
William E Thomas
|
|
|
don; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa
|
Electrical Rough-In | 2/22/2006 | 2/23/2006 | 2/23/2006 | A | PASS |
Jack Frank
|
|
|
don; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa r/i ok
|
Electrical Rough-In | 2/22/2006 | 2/22/2006 | 2/22/2006 | P | FAIL |
Jack Frank
|
|
|
Don -- for reinspection; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong cor. not made 300.4 nail plates called
|
Electrical Rough-In | 2/21/2006 | 2/22/2006 | 2/22/2006 | A | FAIL |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: DONALD CONLEY cor. met contractor, 300.4 nail plates 11/4" high and low voltage, 230.28 guy kit for mast needs too be higher up, 348.42 shall not bury 90 degree flex fittings
|
Application received | | | 2/21/2006 | | DONE |
|
|
|
This permit was created on the web by DONALD CONLEY
|