Final | 4/27/2006 | 4/27/2006 | 4/27/2006 | P | PASS |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: TJ Sturges ok
|
Electrical Rough-In | 2/28/2006 | 3/1/2006 | 3/1/2006 | A | PASS |
Jack Frank
|
|
|
cody; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa
|
Electrical Rough-In | 2/28/2006 | 2/28/2006 | 2/28/2006 | P | PART |
Jack Frank
|
|
|
cody Note: underground; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok
|
Rough-In Permanent Service | 2/27/2006 | 2/28/2006 | 2/28/2006 | P | PASS |
Jack Frank
|
|
|
cody hall; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa u/g & r/i ok p/s o/h new ok
|
Conference | 2/27/2006 | 2/28/2006 | 2/28/2006 | A | PART |
Jack Frank
|
|
|
Please call Cody at ###-####, he will be available for phone calls as early as 7 a.m. We need a trench inspection, first thing in the morning at 2019 Hervey St. This location is 3 row houses, house numbers being 2019, 2021 and 2023. The permit number being ELE06-00674, 00675 and 00676. ; Phone #: ###-#### Internet Inspection Request from: Nicole Richardson
|
Rough-In Permanent Service | 2/24/2006 | 2/27/2006 | 2/27/2006 | A | FAIL |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Nicole Richardson cor. called 300.4 nail plates 11/4", 250.32 needs concrece encased electrode at garage, 225.30,31,32 only 1 circuit or feeder, needs disconnect, at required locatios garage, 312.5(C) shall not use one conn. for all cables at p/s panel needs concrete encased electrode for house, u/g covered before inspection
|
Application received | | | 2/24/2006 | | DONE |
|
|
|
This permit was created on the web by Nicole Richardson
|