Electrical Rough-In | 3/15/2006 | 3/15/2006 | 3/15/2006 | P | PASS |
Bob Reichert
|
|
|
Lloyd; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong corrections made, ri ok
|
Electrical Rough-In | 3/14/2006 | 3/14/2006 | 3/14/2006 | P | FAIL |
Bob Reichert
|
|
|
lloyd ###-#### called cont, left corr notice, 300.4(A)&(D) edge of holes and nm cable shall be 1 1/4" from edge of framing members, 210.11(C) kitchen shall be supplied with at least 2 20a small appliance branch circuits for recpt outlets,210.52(C)(1) recpt outlets shall be installed so that no point along the wall line is more than 24" from an outlet( by sink), 410.16(A) outlet box shall be installed to support luminaire
|
Issue permit | | | 3/14/2006 | | DONE |
|
|
|
|
Application received | | | 3/14/2006 | | |
|
|
|
|