Final | 2/15/2008 | 2/15/2008 | 2/15/2008 | P | PASS |
Bob Reichert
|
|
|
ok to final
|
Permanent Service | 3/28/2006 | 3/28/2006 | 3/28/2006 | A | PASS |
Jack Frank
|
|
|
Ryan ###-#### -- okay for 3-28 AM per Jack Frank; call 1st for access 3-28-06 eus p/s o/h new ok
|
Final | 3/27/2006 | 3/28/2006 | 3/28/2006 | A | CANC |
Jack Frank
|
|
|
Ryan -- call 1st before insp for access; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong /// Cancel per Ryan as suggested by Jack Frank 3-28-06 eus
|
Permanent Service | 3/22/2006 | 3/24/2006 | 3/24/2006 | P | FAIL |
Jack Frank
|
|
|
###-#### corr. met owner, 312.5(A) conn for GEC, 110.3(A) only 1 wire under each grd clamp also istall wires in clamp properly , also 1 wire per lug in panel grd wire solid and stranded, 230.28 guy kit mast, meter too high, 300.10 nipple between meter and panel needs 4 locknuts
|
Issue PAID IN FULL permit | | | 3/22/2006 | | DONE |
|
|
|
|
Application received | | | 3/22/2006 | | |
|
|
|
|