Final | 7/19/2006 | 7/19/2006 | 7/19/2006 | P | PASS |
Bob Reichert
|
|
|
Internet Inspection Request from: Latisha Peltier ok to final
|
Rough-In Permanent Service | 4/20/2006 | 4/20/2006 | 4/20/2006 | A | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 4/20/2006 at 7:06:25 AM. Contact: ###-####. corr made, ric ok, p/s u/g n ok
|
Rough-In Permanent Service | 4/17/2006 | 4/18/2006 | 4/18/2006 | A | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Latisha Peltier called cont, left corr notice, BCC all make-up shall be done, approved set of plans shall be on job, address shall be posted, 334.30 nm cable shall be secured every 4 1/2 ', 334.24 nm bend radius shall be at least 5x diameter, 314.20 boxes shall be flush with finished surface
|
Application received | | | 3/27/2006 | | |
|
|
|
|
Issue & PRINT permit | | | 3/27/2006 | | |
|
|
|
|