Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberELE06-01053
StatusFinaled
Name L & K ELECTRIC
Site Address 2301 N 36TH ST Unit: 101
Project NameNORTHSIDE OFFICE
Customer Number 
ePlanReview 
Description
3-28-06 New building tenant improvement; Owner Supplied Equipment; Init Cert of Value $21,000.00 eus ///Final value is $38,839//8/16/06 LEG
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Third Notice ELE8/4/20068/4/20068/16/2006 DONE
Second Notice has not been responded to.
Second Notice ELE7/6/20067/6/20068/4/2006 DONE
First Notice has not been responded to.
First Notice5/31/20065/31/20067/6/2006 DONE
DetailsPat Lass
Final5/30/20065/31/20065/31/2006APASS
DetailsPat Lass
marvin; Phone #: ###-#### Internet Inspection Request from: Rita DeYoung
I have looked at The T/I also it is ok.
Final5/30/20065/30/20065/30/2006PNH
DetailsWilliam E Thomas
Marvin; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt
no access, called contractor and left notice to reschedule
Electrical Rough-In5/15/20065/16/20065/16/2006APASS
DetailsJim Schmer
per jim s. for a ceiling insp -corrections from bob ok. jms
Electrical Rough-In5/12/20065/15/20065/15/2006AFAIL
DetailsWilliam E Thomas
larura; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
1. no cover inspection for the cieling - hard lid and insulation.
2. must remove for inspection
Stop Work/Reinspection Fee5/15/20065/15/20065/15/2006ADONE
DetailsWilliam E Thomas
dtop work --- hard lids and insulation in the cieling need to be removed for inspection.per jim s. take hold off
Override - Activity Holds  5/15/2006  
Electrical Rough-In3/28/20063/29/20063/29/2006APART
DetailsPat Lass
###-####. Scheduled by a contractor via Hello! on 3/28/2006 at 8:26:42 PM. Contact: ###-####.
walls ok
Electrical Rough-In3/28/20063/28/20063/28/2006PFAIL
DetailsJack Frank
Justin; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong
corr. called 300.4(A)(1)&(D), nail plates and 11/4" for MC and ENT, 330.30(B) 358.30 (A&B) shall strap MC 12" of boxes, EMT 3ft of boxes, 410.67(A B C) shall not use fixture whips for reccess fixtures shall be branch circuit wiring to jbox on fixture
Application received  3/28/2006  
Issue & PRINT permit  3/28/2006  
Owner Supplied Equipment3/28/2006