Third Notice ELE | 10/10/2006 | 10/10/2006 | 3/4/2015 | | DONE |
Tisha Gallop
|
|
|
This permit finaled on the web by ron spen cer
|
Third Notice | | 12/26/2006 | 7/5/2007 | | DONE |
|
|
|
|
Second Notice ELE | 9/13/2006 | 9/13/2006 | 10/10/2006 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice | 7/28/2006 | 7/28/2006 | 9/13/2006 | | DONE |
Jack Frank
|
|
|
|
Final | 7/28/2006 | 7/28/2006 | 7/28/2006 | A | PASS |
Jack Frank
|
|
|
core shell ok
|
Final | 7/27/2006 | 7/27/2006 | 7/27/2006 | P | FAIL |
Bob Reichert
|
|
|
spencer; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called contr, left corr notice, nec 110.22 disconnect marking shall be of sufficient durability to withstand the environment involved,250.104(A) metal water piping shall be bonded, 422.31(B) disconnects shall be installed for hot water heater and dishwasher, 352.30 rnc shall be supported within 3' of conduit body or termination
|
ELE-Aging Inspection | 5/31/2006 | 5/31/2006 | 6/1/2006 | | DONE |
Bob Reichert
|
|
|
called, suc
|
Rough-In Permanent Service | 3/29/2006 | 3/30/2006 | 3/30/2006 | A | PASS |
Jack Frank
|
|
|
ron ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie shell core wiring , called needs conn. for GEC p/s u/g new ok
|
Application received | | | 3/29/2006 | | |
|
|
|
|
Issue & PRINT permit | | | 3/29/2006 | | DONE |
|
|
|
|