Final | 6/7/2006 | 6/7/2006 | 6/7/2006 | P | PASS |
Bob Reichert
|
|
|
nick ###-#### ok to final
|
Rough-In Permanent Service | 4/3/2006 | 4/3/2006 | 4/3/2006 | P | PASS |
Bob Reichert
|
|
|
Re-inspection request. Thanks; Phone #: ###-#### Internet Inspection Request from: Ryan Christensen should check refrigerator recpt box, rest corr made, ric ok, p/s u/g n ok
|
Rough-In Permanent Service | 3/30/2006 | 3/31/2006 | 3/31/2006 | A | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Ryan Christensen called left message, BCC all make-up shall be done, 210.52 (A)(2) receptacles shall be added in any wall space over 2' in width, 110.12(C) there shall be no broken boxes, 300.4(A) edge of holes shall be 1 1/4" from edge of framing member, 725.55(A) class 2&3 cables shall not be run with class 1 conductors
|
Application received | | | 3/30/2006 | | DONE |
|
|
|
This permit was created on the web by Ryan Christensen
|