Permanent Service | 4/18/2006 | 4/19/2006 | 4/19/2006 | A | FAIL |
Jack Frank
|
|
|
Internet Inspection Request from: Tyler Bowen corrections not made and new violations created, 110.26(F)(2) remove bush for p/s clearence, 110.12(A) seal all unused KOs, 240.24(A) breaker spaces over 6ft7" 408.4 label panel, 314.16 box fill new jbox in basement under stairs, 250.104(A)(1) bond hot and cold called fee due posted also
|
Permanent Service | 4/17/2006 | 4/17/2006 | 4/17/2006 | P | FAIL |
Jack Frank
|
|
|
toby Internet Inspection Request from: Tyler Bowen corr. not made and not ready
|
Final | 4/14/2006 | 4/17/2006 | 4/17/2006 | A | FAIL |
Jack Frank
|
|
|
###-#### - toby corr. called 250.8 no sms, 312.5 needs conn for all cables and conductors, 310.15 derate at 50%, 250.52&104 grd within 5 ft of u/g pipe, bond hot and cold.110.26(F)(2) remove bush in front of p/s, 240.24 highest breaker position over 6ft7", 250.64(C) no splice allowed in GEC also remove it from raceway and jbox shall not ID 6 or smaller grds and neuts, cow
|
Conference | 4/4/2006 | 4/4/2006 | 4/4/2006 | P | DONE |
William E Thomas
|
|
|
CALL MIKE DELACY BEFORE HEADING TO SITE; Phone #: ###-#### Internet Inspection Request from: Sean DeLacy talked about working clearences for panels
|
Application received | | | 4/4/2006 | | DONE |
|
|
|
This permit was created on the web by Sean DeLacy
|
Stop Work/Reinspection Fee | 4/19/2006 | 4/19/2006 | | A | |
Jack Frank
|
|
|
Internet Inspection Request from: Tyler Bowen reinspection fee due corrections not made and created new ones
|