Final | 7/27/2006 | 7/27/2006 | 7/27/2006 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Cevyn Recla ok to final
|
Rough-In Permanent Service | 5/31/2006 | 5/31/2006 | 5/31/2006 | P | CANC |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Cevyn Recla wrong house
|
Rough-In Permanent Service | 5/1/2006 | 5/1/2006 | 5/1/2006 | P | PASS |
Bob Reichert
|
|
|
Internet Inspection Request from: Cevyn Recla corr made, ric ok p/s u/g n ok
|
Rough-In Permanent Service | 4/28/2006 | 4/28/2006 | 4/28/2006 | P | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Cevyn Recla called contr, left corr notice, nec 300.4(A)(1) edge of bored holes shall be 1 1/4" from edge of framing members, 314.20 box in combustible material shall be flush with finished surface, BCC all make-up shall be done, Note contractor to change permit to 17 rooms.
|
Application received | | | 4/5/2006 | | DONE |
|
|
|
This permit was created on the web by Cevyn Recla
|