Final | 3/20/2007 | 3/20/2007 | 3/20/2007 | P | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 3/20/2007 at 7:16:45 AM. Contact: ###-####. called contr to chg stranded to solid #8 to bond motors, ok to final
|
Final | 11/7/2006 | 11/7/2006 | 11/7/2006 | P | FAIL |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 11/7/2006 at 10:47:37 AM. Contact: ###-####. called, left corr notice, nec 110.12(A) unused openings shall be closed, 408.4 circuit directory shall be clear, concise, and complete, 680.26(B)(4) pump motors shall be bonded
|
Electrical Rough-In | 6/15/2006 | 6/15/2006 | 6/15/2006 | P | PASS |
Jack Frank
|
|
|
mel - swimming pool ; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley u/g pool bond and equip potential grid ok
|
Electrical Rough-In | 6/6/2006 | 6/7/2006 | 6/7/2006 | A | PART |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 6/6/2006 at 6:25:40 PM. Contact: ###-####. encapsulation only ok needs machine screw and copper lugs, and clean surfaces for pool bonding called left message, also still needs equip. grid
|
Electrical Rough-In | 6/6/2006 | 6/7/2006 | 6/6/2006 | A | CANC |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 6/6/2006 at 6:10:35 PM. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on Jun 6 2006 6:16PM.
|
Conference | 4/13/2006 | 4/13/2006 | 4/13/2006 | P | DONE |
Jack Frank
|
|
|
mel; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok
|
Conference | 4/12/2006 | 4/12/2006 | 4/12/2006 | P | PART |
Jack Frank
|
|
|
OFF ###-#### CELL ###-#### - CRAIG talked with contractor he will call if conference required
|
Issue permit | | | 4/12/2006 | | DONE |
|
|
|
|
Application received | | | 4/12/2006 | | |
|
|
|
|