Final | 10/5/2006 | 10/5/2006 | 10/5/2006 | P | CANC |
Pat Lass
|
|
|
Phone #: ###-#### Internet Inspection Request from: Todd Holbrook Inspection cancelled from web by: Todd Holbrook
|
Final | 9/29/2006 | 9/29/2006 | 9/29/2006 | P | FAIL |
Pat Lass
|
|
|
Phone #: ###-#### Internet Inspection Request from: Todd Holbrook no clearandc in front of disconnect in house and recep behind front door not trimmed out could not open disconnect because it was caulked in
|
Rough-In Permanent Service | 4/19/2006 | 4/19/2006 | 4/19/2006 | A | FAIL |
William E Thomas
|
|
|
Phone #: ###-#### Internet Inspection Request from: Todd Holbrook corrections not made properly for grounding issues.
|
Rough-In Permanent Service | 4/14/2006 | 4/14/2006 | 4/14/2006 | P | FAIL |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Todd Holbrook corr. called left message 300.4 nail plates &11/4" everywhere, 250.148 grd all metal boxes , 314.20 all outside boxes shall be flush with combustible material at time of r/i where siding is on house, 250.32(A)(B)(1) needs electrodes at house also shall meet 250.52(A)(1)or 250.104(A)(1) grd or bond, 314.28 conduit cable entries shall bo 12",plastic jbox basement,225.32 needs disconnect at house either outside or inside where first enters, 314.43,110.3, 314.23 no screws in plastic boxes or LBs
|
Final | 4/14/2006 | 4/14/2006 | 4/14/2006 | P | CANC |
Pat Lass
|
|
|
Phone #: ###-#### Internet Inspection Request from: Todd Holbrook Inspection cancelled from web by: Todd Holbrook
|
Application received | | | 4/14/2006 | | DONE |
|
|
|
This permit was created on the web by Todd Holbrook
|