Final | 8/14/2006 | 8/15/2006 | 8/15/2006 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr made, ok to final
|
Final | 8/10/2006 | 8/11/2006 | 8/11/2006 | A | FAIL |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 8/10/2006 at 2:58:59 PM. Contact: ###-####. called, left corr notice, nec 410.4(D) fixture in tub area (3' horizontally) shall be listed for damp location(master bath), 406.8(C) recpt shall not be installed in tub area(master bath), 406.5 recpt faceplates shall cover opening and seat against mounting surface (island,kitchen), 406.4 kitchen counter recpt shall be securely fastened in place, 314.21 drywall shall be repaired around boxes( compactor and range)
|
Permanent Service | 5/1/2006 | 5/1/2006 | 5/1/2006 | P | CANC |
Bob Reichert
|
|
|
Rick - ###-#### - may have done this on 4/17 per notes please check Inspection cancelled from web by: Rita DeYoung
|
Electrical Rough-In | 4/17/2006 | 4/17/2006 | 4/17/2006 | P | PASS |
Bob Reichert
|
|
|
###-#### - rick called contr about nailplate and light make-up, ric ok, p/s u/g n ok
|
Issue permit | | | 4/17/2006 | | DONE |
|
|
|
|
Application received | | | 4/17/2006 | | |
|
|
|
|