Second Notice ELE | 7/6/2006 | 7/6/2006 | 7/10/2006 | | DONE |
|
|
|
This permit finaled on the web by Todd Holbrook
|
First Notice | 6/7/2006 | 6/7/2006 | 7/6/2006 | | DONE |
Bob Reichert
|
|
|
|
Final | 6/6/2006 | 6/7/2006 | 6/7/2006 | A | PASS |
Bob Reichert
|
|
|
chris ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie signed occ card, ok to cover ceilings and final
|
Rough-In Permanent Service | 4/26/2006 | 4/26/2006 | 4/26/2006 | P | PASS |
Mike Kinnear
|
|
|
chris ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ok cover ri p/s u/g n ok
|
Electrical Rough-In | 4/21/2006 | 4/21/2006 | 4/21/2006 | P | FAIL |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 4/21/2006 at 8:57:14 AM. Contact: ###-####. called contr, left corr notice on front glass, nec 362.30 ent shall be strapped within 3' of box and every 3', 330.30(B) mc cable shall be strapped within 12" of box, 300.4(D) ent shall be 1 1/4" from edge of framing member, 110(F)(1)(a) space equal to width and depth of panel is dedicated from floor to 6' above or structural ceiling- no foreign systems shall be in this space
|
Rough-In Permanent Service | 4/20/2006 | 4/21/2006 | 4/21/2006 | A | NH |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Todd Holbrook called contr, told to call when accessible
|
Application received | | | 4/20/2006 | | DONE |
|
|
|
This permit was created on the web by Todd Holbrook
|